Air changes per hour calculator: home ventilation rate

Calculate how many times per hour your ventilation replaces the air in a home or room, and compare the airflow with the ASHRAE 62.2 minimum for whole-house ventilation.

Updated on
Your inputs

Value out of range

Value out of range

Value out of range

Value out of range

Results

Air changes per hour

0.37 ACH

Meets the minimum airflow

ASHRAE 62.2 minimum airflow

90 cfm

Air changes per hour at the minimum
0.34 ACH
Volume
16,000 cu ft
Minutes to replace the air once
160 min

What air changes per hour mean

Air changes per hour (ACH) is the number of times the air in a space would be fully replaced in one hour at a given ventilation airflow. It turns an airflow in cfm into a figure you can compare between rooms and buildings of different sizes.

The formulas

  • Volume = floor area × ceiling height
  • ACH = airflow (cfm) × 60 ÷ volume (ft³)
  • ASHRAE 62.2 minimum for whole-house mechanical ventilation = 0.03 × floor area (ft²) + 7.5 × (bedrooms + 1) cfm

Worked example

A 2,000 ft² three-bedroom house with 8 ft ceilings and a 100 cfm continuous exhaust fan:

  1. Volume = 2,000 × 8 = 16,000 ft³.
  2. ACH = 100 × 60 ÷ 16,000 = 0.375: the air is replaced about every 2 hours 40 minutes.
  3. ASHRAE 62.2 minimum = 0.03 × 2,000 + 7.5 × 4 = 90 cfm, about 0.34 ACH.
  4. The fan meets the minimum.

Typical values

Situation ACH
Very tight new home without ventilation below 0.1
Whole-house ventilation to ASHRAE 62.2 0.3–0.4
Older, leaky home (natural infiltration) 0.5–1.5
Classroom or office (ASHRAE 62.1) 2–4
Hospital patient room 6
Operating room 15–20

Ventilation and airtightness

Building codes now require new homes to be tested for airtightness, often to 3 to 5 ACH at 50 pascals (ACH50) under the IECC. Natural infiltration is roughly ACH50 ÷ 20, so a tight home leaks only about 0.15 to 0.25 ACH and needs mechanical ventilation to keep indoor air healthy. The ASHRAE 62.2 formula sets that airflow.

Indoor air and infection control

For rooms where people gather, the CDC suggests at least 5 equivalent air changes per hour of clean air. That can combine outdoor air with filtration: a portable HEPA purifier with a clean air delivery rate (CADR) of 200 cfm adds 6 ACH in a 2,000 ft³ room, such as a 250 ft² bedroom with 8 ft ceilings. A CO₂ monitor helps check ventilation; readings below about 800 ppm indicate good fresh air supply.

Energy cost

Every cubic foot of outdoor air must be heated or cooled. A balanced system with an energy recovery ventilator (ERV) or heat recovery ventilator (HRV) recovers 60% to 80% of that energy, which makes generous ventilation affordable in cold and hot climates.

Measuring airflow

Fan ratings assume ideal ducts; real airflow is often 20% to 50% lower. A flow hood, an anemometer at the grille or a simple garbage-bag test gives a better number to enter.

Frequently asked questions

How do you calculate air changes per hour?

ACH = airflow in cfm × 60 ÷ volume in cubic feet. 100 cfm in a 16,000 ft³ house gives 0.375 air changes per hour.

How much ventilation does a house need?

ASHRAE 62.2 sets the whole-house minimum at 0.03 cfm per square foot plus 7.5 cfm per occupant, counted as bedrooms plus one. A 2,000 ft² three-bedroom home needs 90 cfm.

What ACH is recommended for a room?

Homes often run around 0.35 ACH. For infection control, the CDC suggests at least 5 equivalent air changes per hour of clean air in occupied rooms, by combining ventilation and filtration.

Is a higher ACH always better?

Not in winter or summer, because more outdoor air means more heating or cooling. An energy recovery ventilator recovers much of that energy.