Heat loss calculator: how much heat does your house lose?

Estimate the design heat loss of a house through its walls, windows, roof and floor (U × A × ΔT) plus air leakage, to size a furnace or heat pump.

Updated on
Your inputs
sq ft

Value out of range

BTU/h·ft²·°F

Value out of range

sq ft

Value out of range

BTU/h·ft²·°F

Value out of range

sq ft

Value out of range

BTU/h·ft²·°F

Value out of range

sq ft

Value out of range

BTU/h·ft²·°F

Value out of range

ft

Value out of range

Value out of range

°F

Value out of range

Results

Total heat loss

21,240

Heat loss per unit of floor area

14.2 BTU/h per sq ft

Well-insulated home (under about 50 W/m²)
Through walls, windows, roof and floor
14,760
Through air leakage and ventilation
6,480
Share of air leakage
31%
Heat loss coefficient
354.0 BTU/h·°F

Why calculate heat loss

A house loses heat through every surface that separates warm inside air from cold outside air, and through the outside air that leaks in. On the coldest days, the heating system must replace all of that loss. Knowing the design heat loss helps you size a furnace or heat pump correctly and shows which improvements will save the most energy.

The formula

For each building element:

Heat loss = U × A × ΔT

  • U is the U-factor in BTU/h·ft²·°F, the inverse of the assembly’s total R-value.
  • A is the area in square feet.
  • ΔT is the design temperature difference between inside and outside.

Air leakage adds:

Infiltration loss = 0.018 × volume × ACH × ΔT

where 0.018 BTU/ft³·°F is the heat capacity of air, the volume is floor area times ceiling height and ACH is the number of air changes per hour.

Worked example

A 1,500 sq ft single-story house with 8 ft ceilings, a 60 °F design difference and 0.5 air changes per hour:

  • Walls: 1,200 sq ft × 0.06 = 72 BTU/h·°F
  • Windows and doors: 180 sq ft × 0.30 = 54
  • Attic ceiling: 1,500 sq ft × 0.03 = 45
  • Floor: 1,500 sq ft × 0.05 = 75
  • Air leakage: 0.018 × 12,000 ft³ × 0.5 = 108

The total coefficient is 354 BTU/h·°F. Multiplied by 60 °F, the heat loss is 21,240 BTU/h, about 6.2 kW, or 14.2 BTU/h per sq ft. Air leakage accounts for 31% of it, a sign that air sealing would pay off.

Choosing the inputs

  • U-factors: a 2×6 wall with R-19 batts is about 0.06 overall; an R-38 attic about 0.03; ENERGY STAR windows 0.30 or less; old single-pane windows about 1.0.
  • ACH: a tight new house may be 0.2 to 0.35, an average house 0.5, an old leaky house 1.0 or more. A blower-door test measures it.
  • ΔT: indoor temperature (often 70 °F) minus your local 99% heating design temperature, which ranges from above 30 °F along the Gulf Coast to −10 °F or lower in the northern states.

From heat loss to equipment

A furnace or heat pump should cover the design heat loss without a large margin. Oversized equipment cycles on and off, wastes energy and wears out faster. Heat pumps lose capacity as it gets colder, so check the manufacturer’s output at your design temperature.

This is a simplified estimate. A full ACCA Manual J calculation, required by many codes for new equipment, also accounts for duct losses, basement and slab edges, thermal bridges and internal gains. Floors over a crawl space or on a slab lose less than the full ΔT suggests, so the example is slightly conservative.

Frequently asked questions

How is heat loss calculated?

For each wall, window, roof and floor, multiply the area by its U-factor and by the temperature difference between inside and outside. Add the heat carried away by outside air leaking in: 0.018 × the house volume × air changes per hour × the temperature difference, in BTU per hour.

What is a U-factor?

The rate of heat flow through one square foot of a building element for each degree Fahrenheit of difference, in BTU/h·ft²·°F. It is the inverse of the total R-value of the assembly. A 2×6 wall with R-19 insulation has a whole-wall U-factor of about 0.06, because the studs conduct more heat than the insulation, while a typical ENERGY STAR window is around 0.30 or lower.

What temperature difference should I use?

The difference between your indoor temperature, often 70 °F, and your local winter design temperature, which is cold enough to be colder only about 1% of the hours in a year. In much of the northern United States that gives 60 to 80 °F.

Is this a Manual J calculation?

No. ACCA Manual J, which many building codes require for sizing heating and cooling equipment, also accounts for ducts, ground contact, thermal bridges and orientation. This estimate is useful for comparing improvements and for a first check of equipment size.