Solar battery bank calculator for off-grid and backup systems

Size a battery bank from your daily energy use and the days of autonomy you want, with the number of batteries and the solar array needed to recharge it.

Updated on
Your inputs
Wh

Value out of range

days

Value out of range

%

Value out of range

Ah

Value out of range

h

Value out of range

Results

Battery bank capacity

8.33 kWh

Capacity at the system voltage

347 Ah

12 V batteries needed
8
Batteries in series per string
2
Strings in parallel
4
Solar array to recharge daily use (75% system efficiency)
889 W

Sizing a battery bank

An off-grid cabin, an RV or a home backup system needs batteries big enough to cover the hours, or days, when the sun is not shining. Too small and you run out at night or in a cloudy spell; too large and you pay for capacity you never use and may never fully recharge.

The method

  1. Daily energy use in watt-hours: add up each appliance’s watts × hours of use per day.
  2. Days of autonomy: how many days the batteries must cover without sun, typically 1 to 3.
  3. Usable depth of discharge (DoD): how much of the battery you can safely use.
  4. Efficiency: inverter and wiring losses, typically about 90%.

Battery capacity (Wh) = daily use × days ÷ (DoD × efficiency)

Amp-hours = Wh ÷ system voltage

Worked example

A cabin uses 3,000 Wh a day. You want 2 days of autonomy on a 24 V system with lithium batteries used to 80%, and an inverter at 90% efficiency.

  • Capacity = 3,000 × 2 ÷ (0.80 × 0.90) ≈ 8.33 kWh
  • At 24 V: 8,333 ÷ 24 ≈ 347 Ah
  • With 12 V 100 Ah batteries: 2 in series per string × 4 strings in parallel = 8 batteries
  • Solar array to recharge the daily use with 4.5 peak sun hours: 3,000 ÷ (4.5 × 0.75) ≈ 889 W

Battery chemistry

Type Usable DoD Cycle life Notes
LiFePO4 (lithium iron phosphate) 80–100% 3,000–6,000 Light, no maintenance, built-in management system
AGM or gel lead-acid 50% 500–1,500 Cheaper up front, heavy, losses in cold
Flooded lead-acid 50% 1,000–2,000 Needs watering and ventilation

Choosing the system voltage

Daily load or inverter size Voltage
Up to about 1 kW 12 V
1–3 kW 24 V
Above 3 kW, whole-home 48 V

Higher voltage halves the current for the same power, which means thinner cables and lower losses. Most new home battery systems run at 48 V.

Tips

  • Cut the load first: LED lighting, an efficient fridge and avoiding electric heating can halve the battery bank you need.
  • Count winter sun hours when sizing the array for year-round use; they can be half the summer value or less.
  • Add a generator for long cloudy spells rather than buying days of extra batteries.
  • Avoid mixing old and new batteries or different capacities in the same bank.
  • For grid-tied homes, a battery is mainly for backup or for shifting solar power to the evening under time-of-use rates.

Frequently asked questions

How do I size a solar battery bank?

Multiply your daily energy use by the days of autonomy you want, then divide by the usable depth of discharge and the inverter efficiency. 3,000 Wh × 2 days ÷ (0.8 × 0.9) ≈ 8.3 kWh.

How many amp-hours do I need?

Divide the capacity in watt-hours by the system voltage: 8,333 Wh ÷ 24 V ≈ 347 Ah, or eight 12 V 100 Ah batteries wired as four parallel strings of two.

Lithium or lead-acid?

LiFePO4 batteries cost more up front but can use 80% to 100% of their capacity and last 3,000 to 6,000 cycles. Lead-acid batteries should not go below 50% and last a few hundred to about 1,500 cycles.

Which system voltage should I choose?

12 V for small systems up to about 1 kW, 24 V up to about 3 kW and 48 V for larger homes. Higher voltage means lower current, thinner cables and lower losses.