The fire alarm battery calculator gives the standby and alarm ampere-hours, the required capacity with a margin and the standard battery size of a fire alarm system, from the currents and the times of the code.
How the calculation works
- Enter the standby current of the panel and the devices and the standby time required.
- Enter the alarm current with all the horns and strobes on and the alarm time.
- Enter the margin factor. The calculator gives the ampere-hours and the standard battery size.
Example
A fire alarm panel draws 0.45 A in standby for 24 h, that is 10.80 Ah. In alarm it draws 3.2 A for 5 min, that is 3.2 × 5 / 60 = 0.27 Ah. With a margin of 1.2 the required capacity is (10.80 + 0.27) × 1.2 = 13.28 Ah, so you choose the next standard size, an 18 Ah battery.
Why it matters
The calculator helps fire alarm designers, installers, electrical contractors and facility managers to size the batteries of a panel or a power supply, to check an existing system when devices are added and to prepare the submittal.
Good to know
Add up the currents from the data sheets and use the alarm current with all the notification appliances on, since the worst case is the one that counts. Choose a battery whose rated capacity is at the 20 hour rate or at the rate stated by the panel maker, and do not count on the full capacity at a high discharge current. Test the batteries every year, replace them on schedule and label the date of installation on the case. Keep the battery calculation sheet in the project file, with the data sheets it comes from, so that the next change to the system can be checked against it.