The emergency egress lighting calculator gives the number of emergency luminaires, their spacing, the maximum spacing for an even light and the battery energy needed for a path of egress, from the size of the path, the illuminance required and the lumens of the luminaire.
How the calculation works
- Enter the length and the width of the path of egress and the average illuminance required on the floor.
- Enter the lumens of one luminaire, the coefficient of utilization, the light loss factor and the mounting height.
- Enter the power and the duration to get the number of luminaires, the spacing and the battery energy.
Example
A corridor of 150 ft by 6 ft has an area of 900 ft². The code asks for an average of 1 fc, so the luminaires must give 900 lm on the floor. One luminaire of 400 lm gives 400 × 0.45 × 0.8 = 144 lm, and 900 / 144 = 6.25, that is 7 luminaires. The spacing is 150 / 7 = 21.4 ft, within the maximum of 4 × 9 = 36 ft. At 6 W for 1.5 h, the batteries need 63 Wh.
Why it matters
The calculator helps electricians, lighting designers, building owners, safety officers and students to make a first count of the emergency luminaires of a corridor, a stair or an open office, to see how the lumens and the mounting height change the spacing, and to size the batteries before the photometric study.
Good to know
Place a luminaire at each exit door, at each change of direction, near the stairs and at the intersection of corridors, in addition to the spacing found by the calculation. Test the units every month and for the full duration every year, and write down the tests. Keep the paths free of obstacles, and use a photometric layout from the manufacturer to prove the minimum of 0.1 foot-candle.