Emergency egress lighting fixture count and spacing calculator

Enter the length and the width of the path, the illuminance required, the lumens of the luminaire and the mounting height to get the number of emergency luminaires, the spacing and the battery energy.

Updated on
Your inputs
ft

Value out of range

ft

Value out of range

fc

Value out of range

lm

Value out of range

Value out of range

Value out of range

ft

Value out of range

W

Value out of range

h

Value out of range

Results

Emergency luminaires required

7

Area of the path
900 ft²
Spacing of the luminaires
21.4 ft
Even enough: the spacing is within four times the mounting height
Maximum spacing for an even light
36 ft
Battery energy needed
63 Wh

The emergency egress lighting calculator gives the number of emergency luminaires, their spacing, the maximum spacing for an even light and the battery energy needed for a path of egress, from the size of the path, the illuminance required and the lumens of the luminaire.

How the calculation works

  • Enter the length and the width of the path of egress and the average illuminance required on the floor.
  • Enter the lumens of one luminaire, the coefficient of utilization, the light loss factor and the mounting height.
  • Enter the power and the duration to get the number of luminaires, the spacing and the battery energy.

Example

A corridor of 150 ft by 6 ft has an area of 900 ft². The code asks for an average of 1 fc, so the luminaires must give 900 lm on the floor. One luminaire of 400 lm gives 400 × 0.45 × 0.8 = 144 lm, and 900 / 144 = 6.25, that is 7 luminaires. The spacing is 150 / 7 = 21.4 ft, within the maximum of 4 × 9 = 36 ft. At 6 W for 1.5 h, the batteries need 63 Wh.

Why it matters

The calculator helps electricians, lighting designers, building owners, safety officers and students to make a first count of the emergency luminaires of a corridor, a stair or an open office, to see how the lumens and the mounting height change the spacing, and to size the batteries before the photometric study.

Good to know

Place a luminaire at each exit door, at each change of direction, near the stairs and at the intersection of corridors, in addition to the spacing found by the calculation. Test the units every month and for the full duration every year, and write down the tests. Keep the paths free of obstacles, and use a photometric layout from the manufacturer to prove the minimum of 0.1 foot-candle.

The lumens calculator gives the light of a lamp, the illuminance point source calculator gives the light at a point from a source, the occupant load egress width calculator gives the width of the exits and the stairwell pressurization airflow calculator sizes the fan of a smoke-free stair.

Frequently asked questions

What does the code ask for?

Most building codes ask that the path of egress be lit on emergency power for at least 90 minutes, with an average of 1 foot-candle (about 11 lux) along the path and a minimum of 0.1 foot-candle at any point, with a ratio of the maximum to the minimum that does not exceed 40 to 1. Check the exact values in the code of your area.

How does the lumen method work?

The number of luminaires is the illuminance times the area, divided by the lumens of a luminaire, the coefficient of utilization and the light loss factor. The coefficient of utilization shows how much light reaches the floor, and a value of 0.45 is typical for a narrow corridor. The light loss factor allows for the dirt and the ageing of the lamps and the batteries.

What is the maximum spacing?

Even light needs the luminaires to be close enough that the dark spots between them stay above the minimum. A common rule is a spacing of four times the mounting height, and manufacturers give the exact value from their photometric data. If the spacing found by the calculator is larger, add luminaires, or use a wider beam.

What are the limits of the calculator?

The calculator gives an average and not a point-by-point layout. It does not include the exit signs, the stairs and the doors, which need a light at each change of direction, the reflectances, the outdoor paths, the inverters and the testing of the units. Ask the manufacturer for a photometric layout and follow the fire and life safety code.