How many amps does an electric motor draw?

Estimate the full-load current of a single-phase or three-phase motor from its output power, the supply voltage, the efficiency and the power factor.

Updated on
Your inputs

Value out of range

Supply
V

Value out of range

%

Value out of range

Value out of range

Value out of range

Results

Full-load current

6.19 A

For conductor and breaker sizing, the NEC requires the full-load current tables (430.248 and 430.250), not this estimate
Electrical input power
4.19 kW
Apparent power
4.93 kVA
Approximate starting current
43.3 A

Formulas

A motor’s nameplate power is its mechanical output. The electrical power it draws is higher because of losses (efficiency) and reactive power (power factor). The full-load current is:

Single-phase: I = P ÷ (V × efficiency × PF)

Three-phase: I = P ÷ (√3 × V × efficiency × PF)

with P in watts (1 hp = 745.7 W) and V the line-to-line voltage for three-phase.

Example

A 5 hp three-phase motor on 460 V with an efficiency of 89% and a power factor of 0.85 draws about 3,729 ÷ (1.732 × 460 × 0.89 × 0.85) = 6.2 A. Its electrical input is 4.19 kW and its apparent power 4.93 kVA.

Typical values

Motor size Efficiency Power factor at full load
under 1 hp 65% to 80% 0.65 to 0.80
1 to 10 hp 82% to 91% 0.78 to 0.87
10 to 100 hp 91% to 95% 0.85 to 0.90

Premium efficiency motors (NEMA Premium, IE3) are at the top of these ranges. Efficiency and power factor drop at light load.

What the NEC requires

For sizing conductors, short-circuit protection and disconnects, the National Electrical Code (430.6) requires the full-load current from its tables: Table 430.248 for single-phase and 430.250 for three-phase motors. These table values are deliberately conservative: a 5 hp, 460 V three-phase motor is listed at 7.6 A. Overload protection, on the other hand, is sized from the nameplate current. Use this calculator to estimate or check, not to replace the code tables.

Starting current

When started across the line (direct-on-line), an induction motor draws a locked-rotor current of about 6 to 8 times its full-load current for a few seconds. Star-delta starters reduce it to about a third, while soft starters and variable frequency drives limit it further. Size breakers and generators with this inrush in mind.

Tips

  • Measure the actual current with a clamp meter on each phase; unbalanced currents point to a supply or winding problem.
  • A motor drawing much more than its nameplate current is overloaded or failing.
  • Power factor correction capacitors reduce the current drawn from the supply, not the current in the motor itself.

Frequently asked questions

How do you convert horsepower to amps?

For three-phase motors, amps = hp × 746 ÷ (1.732 × volts × efficiency × power factor). For single-phase, leave out the 1.732.

How many amps does a 5 hp motor draw?

About 6 to 8 A at 460 V three-phase, depending on efficiency and power factor. The NEC table lists 7.6 A for conductor sizing.

Should I use the calculated current to size wires?

No. The NEC requires the full-load current from Tables 430.248 and 430.250 for conductors and short-circuit protection; overloads are sized from the nameplate.

How high is motor starting current?

Across-the-line, about 6 to 8 times the full-load current for a few seconds. Soft starters and drives reduce it.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.