Pipe friction loss calculator: Hazen-Williams pressure drop

Calculate the head loss and pressure drop of water flowing in a pipe from flow rate, inner diameter, length and pipe material with the Hazen-Williams equation.

Updated on
Your inputs

Value out of range

Value out of range

Value out of range

Results

Pressure loss

11.08 psi

Head loss

25.56 ft

Loss per 100 ft of pipe
11.08 psi/100 ft
Flow velocity
6.63 ft/s
Velocity within usual limits

Why pressure drops along a pipe

Water rubbing against pipe walls and against itself loses energy. That loss, called friction loss or head loss, shows up as lower pressure at the far end of the pipe. Too much friction loss means weak showers upstairs, sprinklers that do not reach, or a pump that has to work harder.

The Hazen-Williams equation

For water at normal temperatures in full pipes:

hf = 10.67 × L × Q^1.852 ÷ (C^1.852 × d^4.87)

with hf and L in meters, Q in m³/s and d in meters. In US units, the loss per 100 ft is 0.2083 × (100 ÷ C)^1.852 × gpm^1.852 ÷ d^4.8655, with d in inches. Feet of head convert to psi by dividing by 2.31.

Roughness coefficients

Pipe C
PVC, CPVC, PEX, HDPE 150
Copper 140
Lined ductile iron 130
New steel 120
Old galvanized steel 100 or less

Worked example

10 gpm through 100 ft of 3/4 in type L copper (inner diameter 0.785 in):

  1. Head loss ≈ 25.6 ft.
  2. Pressure loss ≈ 25.6 ÷ 2.31 ≈ 11.1 psi.
  3. Velocity ≈ 6.6 ft/s, within the usual limit for cold water.

At 6 gpm in the same pipe, the loss falls to about 4.3 psi, because friction grows with flow to the power 1.85: a 40% cut in flow cuts loss by 61%.

The power of diameter

Friction loss falls with the diameter to the power 4.87. Going from 3/4 in to 1 in type L copper cuts the loss by about 73% at the same flow. On long runs, upsizing the main line is usually the cheapest fix for low pressure.

Fittings and valves

Each elbow, tee and valve adds loss. Add its equivalent length to the pipe length:

Fitting (3/4 in) Equivalent length
90° elbow about 2 ft
Tee, flow through branch about 4 ft
Gate valve, open about 0.5 ft
Check valve 5 to 10 ft

Pressure budget

A typical plumbing design starts from the street or tank pressure, subtracts the elevation (0.433 psi per foot of rise), the water meter and the friction loss, and checks that at least 15 to 20 psi remains at the most remote fixture. Many fixtures need more: a pressure-balanced shower valve works best at 30 psi or more.

Limits

Hazen-Williams applies to water between about 40 and 75 °F in turbulent flow. For hot water, other fluids or small, slow flows, the Darcy-Weisbach equation with the Colebrook friction factor is more accurate.

Frequently asked questions

What is the Hazen-Williams equation?

An empirical formula for friction loss of water in full pipes: hf = 10.67 × L × Q^1.852 ÷ (C^1.852 × d^4.87) in SI units. C depends on the pipe material, from 150 for plastic to 100 for old steel.

How much pressure is lost in a 3/4 in pipe?

About 11 psi per 100 ft at 10 gpm in type L copper, and about 4 psi per 100 ft at 6 gpm.

How do I account for fittings?

Add an equivalent length for each fitting: roughly 2 ft for a 3/4 in elbow, 4 ft for a tee through the branch and 0.5 ft for an open gate valve.

When is Hazen-Williams not valid?

It applies to water near room temperature in turbulent flow. For hot water, other liquids or very small pipes, use the Darcy-Weisbach equation.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.