HVAC superheat and subcooling calculator: readings, usual ranges and coil temperature drop

Enter the line temperatures and the saturation temperatures from the gauges to get the superheat, the subcooling, the temperature drop across the coil and whether they are in the usual ranges.

Updated on
Your inputs
°F

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

Results

Superheat

10.0 °F

In the usual range of 8 to 12 °F for a TXV system
Subcooling
10.0 °F
In the usual range of 8 to 14 °F
Temperature drop across the coil (return − supply)
18.0 °F
In the usual range of 16 to 22 °F
Temperature lift (condensing − evaporating)
66.0 °F

Superheat and subcooling are two readings that show if an air conditioner or heat pump has the right refrigerant charge and is working well. The superheat and subcooling calculator takes the line temperatures and the saturation temperatures from the gauges, and gives both values with the coil temperature drop and the usual ranges.

How the calculation works

  • With the system running, measure the suction line temperature near the service valve and read the evaporator saturation temperature on the suction gauge (from the pressure–temperature chart of the refrigerant).
  • Measure the liquid line temperature and read the condenser saturation temperature on the high-side gauge.
  • Measure the return air and supply air temperatures at the indoor unit.
  • The calculator gives the superheat (suction line − evaporator saturation), the subcooling (condenser saturation − liquid line), the coil temperature drop and the lift, with the usual ranges.

Example

A split system shows a suction line of 52 °F with an evaporator saturation temperature of 42 °F, so the superheat is 10 °F. The liquid line is at 98 °F and the condenser saturation temperature is 108 °F, so the subcooling is 10 °F. Return air is 75 °F and supply air 57 °F, so the coil drop is 18 °F. All three are in the usual ranges for a TXV system.

Why it matters

The calculator helps HVAC technicians, apprentices and homeowners who want to understand a service report to do the arithmetic without mistakes and to read the result against the usual ranges. It saves time on the job and helps to explain a diagnosis, such as a low charge, an overcharge, a restriction or a low airflow.

Good to know

The calculator needs the saturation temperatures from the pressure–temperature chart of your refrigerant, and it does not convert pressures. The ranges are typical for a system with a TXV, and the true target depends on the manufacturer, the metering device and the conditions. The measurements need a clean coil, a good airflow and a steady operation. Refrigerant work needs a certified technician.

The heat pump cost calculator estimates the cost of a system, the AC size calculator sizes the cooling capacity, the dew point calculator gives the condensation temperature of the air, and the heat exchanger LMTD calculator covers the heat transfer of exchangers.

Frequently asked questions

What is superheat?

Superheat is the number of degrees that the refrigerant vapor is hotter than its boiling (saturation) temperature at the pressure of the suction line. It shows that all the liquid has evaporated before the compressor. It is the suction line temperature minus the saturation temperature found from the suction pressure. A little superheat protects the compressor from liquid, and too much means that the evaporator is starved of refrigerant.

What is subcooling?

Subcooling is the number of degrees that the liquid refrigerant is colder than its condensing (saturation) temperature at the high-side pressure. It is the condenser saturation temperature minus the liquid line temperature. Subcooling ensures that only liquid enters the metering device. It is used to check the charge of systems with a TXV, while superheat is used for systems with a fixed orifice.

Which one should I use to check the charge?

For a system with a thermostatic expansion valve (TXV), the subcooling is the main indicator of the charge, and the superheat should stay stable at the setting of the valve. For a fixed orifice or piston system, the superheat is the main indicator, and the target depends on the indoor wet-bulb and the outdoor dry-bulb temperatures from the chart of the manufacturer. Always follow the data plate of the unit.

Are the ranges in the calculator exact?

No. The ranges of 8 to 12 °F of superheat, 8 to 14 °F of subcooling and 16 to 22 °F of coil temperature drop are typical values, and the target of a given system is set by the manufacturer. The reading also depends on the airflow, the load and the outdoor temperature. The work on refrigerant circuits needs a certified technician and the right tools.