Sizing a heat exchanger starts with the log mean temperature difference (LMTD). It is the average driving force for heat transfer between a hot and a cold fluid, and it sets the area needed for a given duty through the relation Q = U × A × LMTD. Enter the four temperatures, the duty and the overall heat transfer coefficient: the calculator gives the LMTD and the required area for counterflow and for parallel flow.
How the calculation works
- Counterflow: ΔT₁ = hot in − cold out, ΔT₂ = hot out − cold in
- Parallel flow: ΔT₁ = hot in − cold in, ΔT₂ = hot out − cold out
- LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂)
- Area A = Q ÷ (U × LMTD)
Example
Hot water enters at 194 °F and leaves at 140 °F. Cold water enters at 68 °F and leaves at 113 °F. The duty is 300,000 BTU/h and U is 90 BTU/h·ft²·°F. In counterflow the LMTD is 76.4 °F and the area needed is 43.6 ft². In parallel flow the LMTD falls to 64.3 °F and the area rises to 51.9 ft², which is 18.9% more.
Where it is used
Designers use the LMTD method for heat exchangers in boilers, chillers, radiators, hot-water heaters, oil coolers and process plants. A technician can compare two proposals, estimate the size of a plate or shell-and-tube exchanger, or check if an existing unit can still deliver its duty after fouling lowers U. When only the inlet temperatures are known, the effectiveness-NTU method is more convenient.
Good to know
Make sure the duty matches the temperature changes and the flow rates: Q equals the flow times the specific heat times the temperature change on each side. The log mean must use differences that are both positive. When the two differences are equal, the LMTD is simply that value. Real exchangers also need a correction factor for multiple passes and cross flow. Fouling, flow distribution and pressure drop can change the real performance.