How big must your heat exchanger be?

Enter the inlet and outlet temperatures, the duty and the U value: get the log mean temperature difference and the area needed for counterflow and parallel flow.

Updated on
Your inputs
°F

Value out of range

°F

Value out of range

°F

Value out of range

°F

Value out of range

BTU/h

Value out of range

BTU/h·ft²·°F

Value out of range

Results

Area needed, counterflow

43.6 ft²

Log mean temperature difference, counterflow
76.41 °F
The temperatures are consistent for a counterflow exchanger
Log mean temperature difference, parallel flow
64.27 °F
Area needed, parallel flow
51.9 ft²
Extra area needed in parallel flow
18.9%

Sizing a heat exchanger starts with the log mean temperature difference (LMTD). It is the average driving force for heat transfer between a hot and a cold fluid, and it sets the area needed for a given duty through the relation Q = U × A × LMTD. Enter the four temperatures, the duty and the overall heat transfer coefficient: the calculator gives the LMTD and the required area for counterflow and for parallel flow.

How the calculation works

  • Counterflow: ΔT₁ = hot in − cold out, ΔT₂ = hot out − cold in
  • Parallel flow: ΔT₁ = hot in − cold in, ΔT₂ = hot out − cold out
  • LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂)
  • Area A = Q ÷ (U × LMTD)

Example

Hot water enters at 194 °F and leaves at 140 °F. Cold water enters at 68 °F and leaves at 113 °F. The duty is 300,000 BTU/h and U is 90 BTU/h·ft²·°F. In counterflow the LMTD is 76.4 °F and the area needed is 43.6 ft². In parallel flow the LMTD falls to 64.3 °F and the area rises to 51.9 ft², which is 18.9% more.

Where it is used

Designers use the LMTD method for heat exchangers in boilers, chillers, radiators, hot-water heaters, oil coolers and process plants. A technician can compare two proposals, estimate the size of a plate or shell-and-tube exchanger, or check if an existing unit can still deliver its duty after fouling lowers U. When only the inlet temperatures are known, the effectiveness-NTU method is more convenient.

Good to know

Make sure the duty matches the temperature changes and the flow rates: Q equals the flow times the specific heat times the temperature change on each side. The log mean must use differences that are both positive. When the two differences are equal, the LMTD is simply that value. Real exchangers also need a correction factor for multiple passes and cross flow. Fouling, flow distribution and pressure drop can change the real performance.

To size the heat needed, use the specific heat calculator. For conduction through a wall, try the heat conduction calculator, and for a room, the heat loss calculator.

Frequently asked questions

What is the log mean temperature difference?

The average temperature gap between the hot and cold fluids along the exchanger, weighted for the fact that the gap changes along the way. It is the driving force used to size the heat transfer area.

Why is counterflow better than parallel flow?

In counterflow, the coldest fluid meets the coolest hot fluid, which keeps a gap along the whole length and allows the cold fluid to leave hotter than the hot fluid's outlet. The average gap is larger, so the area is smaller.

What is a temperature cross?

When the cold outlet is hotter than the hot outlet in a counterflow exchanger, the specified temperatures cannot be reached by a single pass without a cross, which a multipass design must handle with a correction factor.

What about shell and tube exchangers with several passes?

Multipass exchangers need a correction factor F below 1 applied to the LMTD. The calculator gives the counterflow value, which is the upper limit.