Thermocouple EMF calculator: what voltage a thermocouple makes

Choose the type of a thermocouple and enter the hot junction and cold junction temperatures to get the thermoelectric voltage, the cold junction compensation, the sensitivity and the voltage resolution needed for an accurate reading.

Updated on
Your inputs
°F

Value out of range

°F

Value out of range

Results

Thermoelectric voltage (hot minus cold junction)

7.517 mV

Temperature difference
330.0 °F
Sensitivity
22.8 µV/°F
Voltage of the cold junction relative to 0 °C
0.866 mV
Voltage relative to the ice point
8.382 mV
Voltage resolution needed for 0.1 °F
2.28 µV

A thermocouple makes a small voltage that depends on the temperature difference between its hot and cold junctions. The thermocouple EMF calculator gives the thermoelectric voltage of type K, J, T and E, the cold junction compensation, the sensitivity and the resolution of the voltage needed.

How the calculation works

  • Choose the thermocouple type. The calculator uses the average sensitivity between 0 and 200 °C: about 41 µV/°C for type K, 54 for type J, 46 for type T and 67 for type E.
  • Enter the measured temperature at the hot junction and the reference temperature of the cold junction, where the thermocouple wires meet the copper wires of the instrument.
  • The calculator finds the voltage V = S × (Thot − Tref), the open-circuit voltage that the instrument measures, and the voltage of the cold junction relative to 0 °C that the cold junction compensation must add.
  • It gives the sensitivity in µV per degree Fahrenheit and the resolution of voltage needed to read 0.1 °F, to choose an amplifier or an ADC.

Example

A type K thermocouple (41 µV/°C) measures an oven at 400 °F with the cold junction at 70 °F. The temperature difference is 330 °F, or 183.3 °C. The thermoelectric voltage is 41 × 183.3 = 7,517 µV = 7.517 mV. The cold junction at 70 °F (21.1 °C) adds a compensation voltage of 0.866 mV, so the voltage relative to the ice point is 8.382 mV. The sensitivity is 22.8 µV/°F, and a resolution of 2.28 µV is needed to read 0.1 °F.

Why it matters

The calculator helps instrumentation and control engineers, electronics designers, HVAC technicians, makers and students to estimate the signal of a thermocouple, to check a reading with a multimeter, and to size the amplifier and the ADC. It also shows why the cold junction matters.

Good to know

Always compensate the cold junction, and keep the reference sensor next to the terminal block. Use shielded, twisted extension wire of the right type. Keep the junction away from electrical noise, and use a low-noise amplifier or an ADC with at least 16 bits. Use the standard tables or a polynomial for accurate work.

The PT100 RTD calculator covers a more accurate sensor, the Wheatstone bridge calculator covers resistive sensors, the ADC resolution calculator gives the step of an ADC and the op-amp gain calculator sets the amplifier.

Frequently asked questions

How does a thermocouple work?

A thermocouple is made of two wires of different metals joined at one end, the hot junction. When the junction is at a different temperature from the other ends, a small voltage appears, by the Seebeck effect. It is proportional to the temperature difference, and its size is a few tens of microvolts per degree. Thermocouples are cheap, rugged and cover a wide temperature range, from cryogenic to above 1,500 °C.

What is the cold junction?

The voltage depends on the difference between the hot junction and the point where the thermocouple wires connect to the instrument, the cold (or reference) junction. To read the absolute temperature, the instrument measures the temperature of that connection with a sensor and adds the matching voltage. This is the cold junction compensation. A mistake of 1 °C in the reference gives a mistake of 1 °C in the reading.

Which type should I choose?

Type K is the general purpose choice, from −200 to 1,250 °C. Type J is used up to 750 °C but its iron wire rusts. Type T is accurate at low temperatures, down to −200 °C, and is used in food and cryogenics. Type E gives the highest signal and is good at low temperatures. Types R, S and B, with platinum, are used above 1,000 °C. Use extension wires of the same type to the instrument.

What are the limits of this calculator?

The relationship between the voltage and the temperature is not linear. The calculator uses the average sensitivity between 0 and 200 °C, so the error can reach 3% to 5% at a high temperature, and more at a low temperature. For an accurate reading, the instrument uses the polynomial of the standard (ITS-90) for the type. The calculator is good for the order of magnitude, the amplifier gain and the resolution needed.

Was this calculator helpful?