A thermocouple makes a small voltage that depends on the temperature difference between its hot and cold junctions. The thermocouple EMF calculator gives the thermoelectric voltage of type K, J, T and E, the cold junction compensation, the sensitivity and the resolution of the voltage needed.
How the calculation works
- Choose the thermocouple type. The calculator uses the average sensitivity between 0 and 200 °C: about 41 µV/°C for type K, 54 for type J, 46 for type T and 67 for type E.
- Enter the measured temperature at the hot junction and the reference temperature of the cold junction, where the thermocouple wires meet the copper wires of the instrument.
- The calculator finds the voltage V = S × (Thot − Tref), the open-circuit voltage that the instrument measures, and the voltage of the cold junction relative to 0 °C that the cold junction compensation must add.
- It gives the sensitivity in µV per degree Fahrenheit and the resolution of voltage needed to read 0.1 °F, to choose an amplifier or an ADC.
Example
A type K thermocouple (41 µV/°C) measures an oven at 400 °F with the cold junction at 70 °F. The temperature difference is 330 °F, or 183.3 °C. The thermoelectric voltage is 41 × 183.3 = 7,517 µV = 7.517 mV. The cold junction at 70 °F (21.1 °C) adds a compensation voltage of 0.866 mV, so the voltage relative to the ice point is 8.382 mV. The sensitivity is 22.8 µV/°F, and a resolution of 2.28 µV is needed to read 0.1 °F.
Why it matters
The calculator helps instrumentation and control engineers, electronics designers, HVAC technicians, makers and students to estimate the signal of a thermocouple, to check a reading with a multimeter, and to size the amplifier and the ADC. It also shows why the cold junction matters.
Good to know
Always compensate the cold junction, and keep the reference sensor next to the terminal block. Use shielded, twisted extension wire of the right type. Keep the junction away from electrical noise, and use a low-noise amplifier or an ADC with at least 16 bits. Use the standard tables or a polynomial for accurate work.
Related tools
The PT100 RTD calculator covers a more accurate sensor, the Wheatstone bridge calculator covers resistive sensors, the ADC resolution calculator gives the step of an ADC and the op-amp gain calculator sets the amplifier.