What a pressure tank does
A private well pump does not run every time you open a tap. It fills a pressure tank, in which a rubber bladder or diaphragm separates the water from a cushion of compressed air. As you use water, the air pushes it out. When the pressure falls to the cut-in pressure, the pressure switch starts the pump; when it reaches the cut-out pressure, the pump stops.
Drawdown
The water delivered between the cut-out and cut-in pressures is the drawdown. Because air compresses according to Boyle’s law, the drawdown is only a fraction of the tank’s volume:
Drawdown factor = (precharge + atm) × (1 ÷ (cut-in + atm) − 1 ÷ (cut-out + atm))
with pressures in absolute terms (atmospheric pressure, about 14.7 psi, added to the gauge readings). The precharge, the air pressure with the tank empty of water, is usually set 2 psi below the cut-in pressure.
| Pressure switch | Typical drawdown factor |
|---|---|
| 20/40 psi | about 0.34 |
| 30/50 psi | about 0.30 |
| 40/60 psi | about 0.26 |
| 50/70 psi | about 0.23 |
Sizing the tank
Most pump makers recommend that the pump run at least one minute each time it starts, sometimes two minutes for larger pumps. The drawdown needed is then the pump flow rate × the minimum run time, and:
Tank volume = drawdown needed ÷ drawdown factor
Example
A 10 gpm pump on a 40/60 switch, with a 38 psi precharge, has a drawdown factor of about 0.26. For a one-minute run time, it needs 10 gallons of drawdown, so a tank of at least 39 gallons. A 44-gallon tank would be a common choice.
Maintenance
- Check the precharge once or twice a year with the pump off and the water drained from the tank, using a tire gauge on the air valve.
- If water comes out of the air valve, the bladder is ruptured and the tank must be replaced.
- Rapid on-off cycling of the pump is the classic sign of a waterlogged tank or a lost precharge.
Variable-speed pumps
Constant-pressure systems with a variable-speed drive adjust the pump speed to demand and can work with a much smaller tank. Follow the manufacturer’s sizing for those systems.