Bathroom fan CFM calculator

Size a bathroom exhaust fan from the floor area for small rooms, or from the fixtures for large ones, and compare with the air change method.

Updated on
Your inputs
ft

Value out of range

ft

Value out of range

ft

Value out of range

Value out of range

Value out of range

Value out of range

Value out of range

Results

Recommended fan (area or fixture method)

80 CFM

In cubic meters per hour
136 m³/h
Alternative: 8 air changes per hour
85 CFM
Room volume
640 cu ft

A bathroom fan removes the moisture of showers and baths before it condenses on walls and ceilings, where it causes mold, peeling paint and rot. It also clears odors. Fans are rated in cubic feet per minute (CFM), and the Home Ventilating Institute (HVI) gives two simple rules for choosing one.

The HVI rules

Bathrooms up to 100 sq ft: 1 CFM per square foot of floor, with a minimum of 50 CFM. This assumes an 8 ft ceiling.

Bathrooms over 100 sq ft: add up the fixtures:

Fixture CFM
Toilet 50
Shower 50
Bathtub 50
Jetted tub 100

A separate toilet room or a closed shower enclosure should get its own fan of at least 50 CFM.

The air change method

Another approach is to replace the air 8 times an hour: CFM = room volume (cu ft) × 8 ÷ 60. It is useful for bathrooms with high ceilings, where the area rule underestimates the volume.

Example

An 8 × 10 ft bathroom (80 sq ft) needs an 80 CFM fan. With an 8 ft ceiling, the air change method gives 85 CFM, so a standard 80 CFM fan is the right choice.

Codes

The International Residential Code requires bathroom exhaust of at least 50 CFM for intermittent fans or 20 CFM for continuous ones, vented to the outside, never into the attic or a wall cavity.

Getting the rated airflow

A fan only delivers its rated CFM with a short, smooth duct. Long runs, flexible duct and many elbows can halve the airflow.

  • Use the duct size the fan was designed for (often 4 in; 6 in for larger fans) and keep runs short.
  • Prefer smooth rigid duct and insulate it in cold attics to prevent condensation.
  • Terminate through the roof or a wall with a damper.

Noise and controls

Fans are rated in sones: 1 sone or less is quiet, 3 sones is like an office. A quiet fan gets used. A humidity-sensing switch or a timer keeps the fan running for 20 minutes after a shower, long enough to clear the moisture.

Frequently asked questions

What size bathroom fan do I need?

1 CFM per square foot for bathrooms up to 100 sq ft, with at least 50 CFM.

What size fan for a large bathroom?

Add 50 CFM per toilet, shower and tub and 100 CFM per jetted tub.

How long should a bathroom fan run after a shower?

About 20 minutes, so a timer or humidity switch helps.

Can a bathroom fan vent into the attic?

No. Codes require venting to the outside.