Circuit breaker size calculator: which breaker for your load?

Enter the load in watts, the voltage and the type of load to get the current, the minimum breaker rating, the standard breaker size and the share of the breaker that the load uses.

Updated on
Your inputs

Value out of range

Value out of range

Results

Standard breaker size

30 A

Load current as a share of the breaker

76%

Within 80% for continuous loads
Load current
22.92 A
Minimum breaker rating
28.6 A

A breaker that is too small trips for no reason, and one that is too large leaves the wire unprotected. This circuit breaker size calculator takes the load power, the voltage, the number of phases, the power factor and the type of load to give the current, the minimum breaker rating, the standard breaker size and the share of the breaker that the load uses.

How the calculation works

  • Load current = power ÷ (voltage × power factor). For a three-phase load the voltage is multiplied by √3 (1.732).
  • Minimum breaker rating = load current × the load factor: 1.0 for a load that is not continuous, and 1.25 for a continuous load that runs 3 hours or more, as in NEC 210.20 and 215.3.
  • Standard breaker size = the next standard rating at or above the minimum (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A and so on).
  • Share of the breaker = load current ÷ breaker rating. A continuous load should stay at or under 80%.

Example

An electric water heater of 5,500 W runs on 240 V single phase. The current is 5,500 ÷ 240 = 22.9 A. It heats for long periods, so the 125% rule applies and the minimum rating is 28.6 A. The next standard size is a 30 A breaker. The load uses 76% of it, which is below 80%.

Why it matters

The question comes up when you install a heater, an EV charger, a hot tub, a workshop machine or a heat pump, and when you check that an existing circuit can take a new appliance. The calculation shows the breaker and tells you what wire size to look at next. An electrician will do the same arithmetic.

Good to know

This is a guide and not a design. The breaker must also fit the wire, the terminals and the rules for motors, air conditioners, welders and other loads, which have their own tables and sometimes allow a larger breaker for the starting current. Appliance labels give the exact minimum circuit ampacity and the maximum breaker size, and these values take precedence over the calculation. Local codes may add rules, such as arc-fault or ground-fault protection. A licensed electrician should install and inspect work on a panel.

The wire size calculator picks the conductor for the breaker, the watts to amps calculator converts the load and the electrical panel upgrade cost calculator estimates the price of a bigger panel.

Frequently asked questions

How do you size a circuit breaker?

Find the load current by dividing the power by the voltage. For a continuous load, multiply it by 125%, and choose the next standard breaker size above the result. Then check that the wire is rated for at least the breaker rating.

What counts as a continuous load?

A load that runs for 3 hours or more at its maximum current, such as an EV charger, a water heater, a space heater, lighting in a shop or a heat pump compressor. The breaker is then loaded to no more than 80% of its rating.

What are the standard breaker sizes?

In the United States the standard ratings are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350 and 400 amps. The 15, 20 and 30 A ratings are the most common in homes.

Can I use a bigger breaker to stop it from tripping?

No. The breaker protects the wire. A larger breaker on a wire that is too small lets the wire overheat before the breaker trips. If a breaker trips often, find the cause or put the load on a circuit with a larger wire.