How many amps does your appliance draw?

Enter the power, the voltage and the power factor: get the current in amps for DC, single-phase or three-phase AC, the apparent power and the 125% continuous-load figure.

Updated on
Your inputs

Value out of range

V

Value out of range

Value out of range

Results

Current

15.00 A

Needs a 20 A circuit for a continuous load
Apparent power
1.800 kVA
Current with a 125% margin (continuous load)
18.75 A

Electrical devices are rated in watts, but cables, breakers and plugs are rated in amps. This calculator converts one to the other for direct current, single-phase AC and three-phase AC. Enter the power, the voltage and, for AC, the power factor: you get the current, the apparent power in kVA and the current with a 125% margin that is used for continuous loads.

How the calculation works

  • Direct current: amps = watts ÷ volts
  • Single-phase AC: amps = watts ÷ (volts × power factor)
  • Three-phase AC: amps = watts ÷ (√3 × line voltage × power factor)
  • Apparent power (VA) = watts ÷ power factor
  • Continuous load: amps × 1.25

Example

A heater of 1,800 W is plugged into a 120 V single-phase supply with a power factor of 1. The current is 15 A, and the apparent power is 1.8 kVA. With a 125% margin for a continuous load, the circuit must be sized for 18.75 A, which means a 20 A circuit rather than a 15 A one. The same heater at 240 V would draw only 7.5 A.

Where it is used

Homeowners check whether an appliance fits a circuit, electricians size breakers and cables, and installers of solar panels, batteries and generators convert between watts and amps every day. For motors, the nameplate gives the current, and the power factor and efficiency explain why it is higher than the shaft power suggests. In three-phase systems, the current per phase is lower than it would be in single-phase for the same power, which is why industry uses them.

Good to know

Use the voltage that applies: line-to-line for three-phase, and the actual voltage under load, which can be a few percent below the nominal one. Starting currents of motors can be several times higher than the running current. Never add loads to a circuit without checking the total, and have a qualified electrician do any work on fixed wiring. The result is a calculation, not a safety certificate.

For the current of a motor, use the motor current calculator, and for the load on a circuit, the circuit load calculator. The three-phase power calculator and the power factor correction calculator cover the other conversions.

Frequently asked questions

How do you convert watts to amps?

Divide the power by the voltage: amps = watts ÷ volts for direct current. For single-phase AC, also divide by the power factor. For three-phase AC, divide by 1.732 times the line voltage times the power factor.

Why does the power factor matter?

In AC circuits with motors or transformers, the current is higher than power ÷ voltage suggests, because part of it does no work. A lower power factor means more amps for the same watts.

What is the 125% margin?

In US practice, a continuous load, one that runs for three hours or more, should not exceed 80% of the breaker rating, which is the same as sizing the circuit for 125% of the load.

Can I use this to choose a wire?

The current is the first step. The wire size also depends on the length, the insulation, the temperature and the local code, so confirm the choice with the rules in force or an electrician.