The ground fault loop impedance calculator gives the ground fault current of a branch circuit, compares it with the instantaneous trip current of the breaker and shows the voltage on the enclosure during the fault.
How the calculation works
- Enter the voltage to ground, the one-way length of the circuit and the sizes of the phase and grounding conductors.
- Enter the source impedance up to the panel, the breaker rating and its instantaneous trip setting.
- The calculator gives the loop impedance, the ground fault current, the ratio to the trip current and the voltage on the enclosure.
Example
A 120 V branch circuit of 100 ft one way uses 12 AWG for the phase and for the grounding conductor (1.93 Ω per 1000 ft), with 0.05 Ω of source impedance and a 20 A breaker set to trip instantly at 10×. Each conductor has 0.193 Ω, so the loop impedance is 0.05 + 0.193 + 0.193 = 0.436 Ω. The ground fault current is 120 / 0.436 = 275 A, which is 1.38 times the trip current of 200 A, so the breaker trips instantly. The enclosure rises to 53.1 V until it does.
Why it matters
The calculator helps electricians, designers, inspectors and students to check that a long branch circuit, such as a pump, a light pole or a remote outlet, will clear a ground fault fast, and to choose a larger grounding conductor or a different breaker when it will not.
Good to know
Use the one-way length of the whole run, from the panel to the farthest point, and the sizes of the conductors that are really installed. Include the upstream impedance, because a weak source gives a lower fault current. Use the maximum trip setting, because a breaker may need up to the high end of its range to trip instantly. If the ratio is below 1, increase the size of the phase and grounding conductors, shorten the run or use a breaker with a lower trip setting, or a ground fault device. Always measure the real loop impedance when the circuit is commissioned.