Ground fault loop impedance and breaker trip calculator

Enter the voltage, the circuit length, the conductor sizes, the source impedance and the breaker to get the ground fault current and check that the breaker trips instantly.

Updated on
Your inputs
V

Value out of range

ft

Value out of range

Ω

Value out of range

A

Value out of range

× rating

Value out of range

Results

Ground fault current

275 A

Resistance of the phase conductor
0.193 Ω
Resistance of the grounding conductor
0.193 Ω
Total loop impedance
0.436 Ω
Fault current to the trip current
1.38
The breaker trips instantly on a ground fault
Voltage on the grounded enclosure
53.1 V

The ground fault loop impedance calculator gives the ground fault current of a branch circuit, compares it with the instantaneous trip current of the breaker and shows the voltage on the enclosure during the fault.

How the calculation works

  • Enter the voltage to ground, the one-way length of the circuit and the sizes of the phase and grounding conductors.
  • Enter the source impedance up to the panel, the breaker rating and its instantaneous trip setting.
  • The calculator gives the loop impedance, the ground fault current, the ratio to the trip current and the voltage on the enclosure.

Example

A 120 V branch circuit of 100 ft one way uses 12 AWG for the phase and for the grounding conductor (1.93 Ω per 1000 ft), with 0.05 Ω of source impedance and a 20 A breaker set to trip instantly at 10×. Each conductor has 0.193 Ω, so the loop impedance is 0.05 + 0.193 + 0.193 = 0.436 Ω. The ground fault current is 120 / 0.436 = 275 A, which is 1.38 times the trip current of 200 A, so the breaker trips instantly. The enclosure rises to 53.1 V until it does.

Why it matters

The calculator helps electricians, designers, inspectors and students to check that a long branch circuit, such as a pump, a light pole or a remote outlet, will clear a ground fault fast, and to choose a larger grounding conductor or a different breaker when it will not.

Good to know

Use the one-way length of the whole run, from the panel to the farthest point, and the sizes of the conductors that are really installed. Include the upstream impedance, because a weak source gives a lower fault current. Use the maximum trip setting, because a breaker may need up to the high end of its range to trip instantly. If the ratio is below 1, increase the size of the phase and grounding conductors, shorten the run or use a breaker with a lower trip setting, or a ground fault device. Always measure the real loop impedance when the circuit is commissioned.

The wire size voltage drop calculator sizes the conductor for the drop, the ground rod resistance calculator gives the earth resistance, the transformer fault current calculator gives the available fault current and the cable short-circuit withstand calculator checks the heating of the cable.

Frequently asked questions

What is the ground fault loop?

A ground fault current leaves the source through the phase conductor, reaches the fault at a metal enclosure, and returns through the equipment grounding conductor to the source. The impedance of this loop sets the fault current. A long run or a small grounding conductor gives a low current, and the breaker may not trip fast enough.

What does the calculator check?

The current is the voltage divided by the loop impedance, which is the source impedance plus the resistance of the phase and grounding conductors. It is then compared with the current that makes the breaker trip instantly, which is the rating times the trip setting, often 5 to 10 times for a thermal-magnetic breaker. If the current is higher, the breaker trips in a fraction of a second.

Why is the enclosure voltage shown?

While the fault lasts, the grounded enclosure is at the voltage drop in the grounding conductor, which is the fault current times its resistance. A short clearing time makes this voltage safe. The value helps you to see why a small grounding conductor on a long circuit is a hazard.

What does the calculator leave out?

The calculator leaves out the reactance of the conductors, the resistance of the fault itself, the contact resistance at the connections, the heating of the conductors during the fault and the tolerance of the trip setting of the breaker. For long circuits and large conductors, use the data of the manufacturer and a short circuit study.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.