Fans follow simple scaling rules that let you predict the effect of a speed change without a new test. The fan affinity laws calculator takes the current and new speed, the current and new impeller diameter, and the current airflow, pressure and power, and gives the new airflow, the new static pressure, the new shaft power, the change in power and the speed ratio.
How the calculation works
- Enter the current and new fan speeds in rpm. The impeller diameters can stay equal if only the speed changes.
- Enter the current airflow, static pressure and shaft power from the fan curve or a measurement.
- The affinity laws scale the values: airflow × (N₂/N₁) × (D₂/D₁)³, pressure × (N₂/N₁)² × (D₂/D₁)² and power × (N₂/N₁)³ × (D₂/D₁)⁵.
- Check the new shaft power against the motor rating, since power grows with the cube of the speed.
Example
A fan runs at 1,200 rpm and moves 2,000 CFM at 1.5 in. wg with 1 hp at the shaft. Raising the speed to 1,500 rpm gives a ratio of 1.25. Airflow rises to 2,500 CFM, pressure to 1.5 × 1.25² = 2.34 in. wg and power to 1 × 1.25³ = 1.95 hp, which is 95 % more. A speed increase of 25 percent nearly doubles the power draw, which is why a small speed reduction saves so much energy.
Why it matters
The laws show that fan speed is a strong lever on energy use. A small increase to get a bit more air can overload a motor, while a modest reduction in speed gives a large saving. They also help size a drive or a motor when you change the speed of an existing fan, and they check a vendor’s claims.
Good to know
The laws assume the same fan, the same air density and a system that scales with the flow squared. In a real duct with a fixed damper or filter loading, the operating point may not follow the curve exactly. Check the motor rating, the maximum safe speed of the wheel and the noise, which rises steeply with speed, before changing a fan.
Related tools
The bathroom fan and ceiling fan calculators help choose a fan, the duct size calculator checks that the duct suits the airflow, and the fan cost calculator estimates the running cost of the power found here.