Ground rod resistance calculator: resistance to earth from soil resistivity, rod length and diameter

Enter the soil resistivity and the length and diameter of a vertical ground rod to get its resistance to earth, the effect of a longer rod and the ground potential rise for a given fault current.

Updated on
Your inputs
Ω·m

Value out of range

ft

Value out of range

in

Value out of range

A

Value out of range

Results

Resistance to ground of one rod

33.09 Ω

Above 25 Ω: add rods, drive them deeper or improve the soil
Resistance if the rod is twice as long
18.35 Ω
Ground potential rise at the rod
33.1 kV

A ground rod is only as good as its resistance to earth. The ground rod resistance calculator uses Dwight’s formula to give the resistance of a vertical rod from the soil resistivity, the length and the diameter, with the effect of a longer rod and the ground potential rise for a given fault current.

How the calculation works

  • Enter the resistivity of the soil in Ω·m: about 100 for a moist clay or loam, 500 to 1,000 for dry sand or gravel, 10 to 50 for wet soil.
  • Enter the length of the rod that is in the ground and its diameter. The usual rod is 10 ft long and 5/8 in in diameter.
  • The calculator applies Dwight’s formula for a vertical rod, R = ρ / (2πL) × (ln(4L / a) − 1), where a is the radius of the rod.
  • Enter the current of a fault or a lightning strike to get the ground potential rise at the rod, V = I × R.

Example

A rod of 10 ft (3.048 m) and 5/8 in in soil of 100 Ω·m has a resistance of 100 / (2π × 3.048) × (ln(4 × 3.048 / 0.0079375) − 1) = 33.09 Ω. This is above 25 Ω, so a second rod is needed. With a rod of 20 ft, the resistance is 18.35 Ω, a drop of 45 % only. A current of 1,000 A raises the potential of the rod by 33.1 kV.

Why it matters

The calculator helps electricians, engineers, solar and telecom installers and homeowners to check if one rod is enough, to compare rod lengths, and to understand the effect of dry soil on the grounding of a house, a pole or an antenna.

Good to know

The formula is for a single vertical rod in a uniform soil. Real soils have layers, the resistivity changes with the weather, and several rods interact. The result is an estimate for the design, and it must be checked by a measurement on site. The calculator is not a design for the safety of a high-voltage installation, which needs a study of the step and touch voltages. Follow the local electrical code and have a qualified person do the work.

The lightning protection cost calculator estimates the price of a system, the lightning distance calculator finds how far a strike is, the voltage divider calculator and the resistors calculator cover simple resistive circuits.

Frequently asked questions

How is the resistance of a ground rod calculated?

Dwight’s formula, R = ρ/(2πL) × (ln(4L/a) − 1), gives the resistance of a vertical rod driven into a uniform soil. It is proportional to the soil resistivity ρ and decreases with the length L. It depends only weakly on the diameter, because the current spreads out into the soil: doubling the diameter lowers the resistance by only 10 % or so. The formula was published in 1936 and is used in IEEE Std 142 and in many codes.

Why does a longer rod help only a little?

The current leaves the rod in all directions, and most of the resistance is in the soil close to the rod. Doubling the length lowers the resistance by 40 to 45 %, not by half. Adding a second rod helps more if it is far enough from the first: at a spacing of at least twice the length, the two rods act almost as two resistors in parallel. Two rods placed side by side share the same soil and help much less.

What is a good value?

The US National Electrical Code (250.53) asks for a single electrode of 25 Ω or less, or a second electrode. Telecommunications and sensitive electronics often need 5 Ω or less, and substations need an even lower value for safety. Lightning protection asks for a low impedance and a network of electrodes, not only a low resistance. The only way to know the real value is to measure it with a ground resistance tester, by the fall of potential method.

What affects the soil resistivity?

Moisture, the amount of salts, the temperature and the type of soil. Resistivity changes with the season: it rises in a dry summer and in frozen soil, so a rod that is good in spring may not be in winter. Layers of soil with different resistivity change the result, and a measurement of the resistivity by the Wenner method gives an average value. Chemical rods and bentonite can lower the resistance in poor soil.