Skip to content
Omnikalc

Kitchen hood exhaust airflow calculator: minimum exhaust rate of a commercial kitchen hood

Enter the hood length, the duty of the cooking equipment and the type of hood to get the minimum exhaust rate per foot, the total exhaust airflow, the make-up air and the round duct diameter.

Updated on
Your inputs
ft

Value out of range

Results

Total exhaust airflow

3,600 cfm

Minimum exhaust rate per length of hood
300 cfm/ft
Make-up air (80% of the exhaust)
2,880 cfm
Diameter of a round duct at 1,500 ft/min
21.0 in

The kitchen hood exhaust airflow calculator gives the minimum exhaust flow of a commercial kitchen hood from its length, the duty of the cooking equipment and the type of hood, with the make-up air and the round duct diameter at a typical velocity.

How the calculation works

  • Enter the length of the hood over the cooking line.
  • Choose the duty of the cooking equipment under the hood: light, medium, heavy or extra-heavy.
  • Choose the type of hood: wall-mounted canopy, single island or double island.
  • The calculator finds the minimum exhaust rate per foot of hood from the table of the mechanical code, the total exhaust airflow, the make-up air and the diameter of a round duct.

Example

A wall-mounted canopy hood of 12 ft is over medium-duty equipment (ranges, griddles and fryers). The code table gives 300 cfm per foot, so the total exhaust is 12 × 300 = 3,600 cfm. The make-up air is 80% of that, 3,600 × 0.8 = 2,880 cfm. A round duct at 1,500 ft/min needs an area of 3,600 / 1,500 = 2.4 ft², or 345.6 in², which is a diameter of 21.0 in.

Why it matters

The calculator helps restaurant owners, kitchen designers, mechanical engineers, contractors and inspectors to estimate the airflow of a new hood, to size the exhaust fan and the make-up air unit and to prepare the permit. It gives the code starting values before the choice of the listed hood.

Good to know

Use the duty of the hottest appliance under the hood to set the rate for the entire hood. Add to the length of the hood the overhang required on the open sides. Keep the duct velocity within 500 to 2,500 ft/min and respect the clearances and the grease duct rules. Balance the make-up air to keep the kitchen at a slight negative pressure, and check the code adopted locally.

The bathroom fan calculator covers small exhaust fans, the air changes calculator covers ventilation rates, the duct size calculator sizes ducts and the HRV installation cost calculator covers heat recovery ventilators.

Frequently asked questions

What is a Type I hood?

A Type I hood is the exhaust hood required by the codes over commercial cooking equipment that produces grease-laden vapors, such as fryers, griddles, ranges and broilers. It captures and removes the heat, smoke and grease with a listed hood, a grease filter and a duct with a fire suppression system. A Type II hood is for steam, heat and odors only, and does not need the same construction.

How is the exhaust rate set?

The International Mechanical Code gives the minimum exhaust flow per linear foot of hood in a table, based on the duty of the equipment and on the type of hood: for example from 200 cfm per foot for a wall-mounted canopy over light-duty equipment to 700 cfm per foot for a single island hood over extra-heavy-duty equipment. The more heat and effluent the appliance produces, the more air is needed to capture it.

Why is make-up air needed?

The exhaust removes a large volume of air from the kitchen, and the same amount must be brought back, or the building goes under negative pressure. That makes the doors hard to open, pulls the combustion gases down the flues, and reduces the capture of the hood. The codes require the make-up air to be about 80% of the exhaust, or the rest comes from the dining room transfer air, and often it is heated or cooled in cold or hot climates.

What are the limits of the calculator?

The table gives the code minimum. The actual exhaust rate is the one listed for the hood in the manufacturer’s test, which can be lower if the hood is listed for a lower rate, and the design must also consider the cross drafts and the position of the equipment. The calculator uses the typical values of the IMC. The local code and the fire marshal decide the requirements, and the system needs a qualified mechanical designer.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.