The kitchen hood exhaust airflow calculator gives the minimum exhaust flow of a commercial kitchen hood from its length, the duty of the cooking equipment and the type of hood, with the make-up air and the round duct diameter at a typical velocity.
How the calculation works
- Enter the length of the hood over the cooking line.
- Choose the duty of the cooking equipment under the hood: light, medium, heavy or extra-heavy.
- Choose the type of hood: wall-mounted canopy, single island or double island.
- The calculator finds the minimum exhaust rate per foot of hood from the table of the mechanical code, the total exhaust airflow, the make-up air and the diameter of a round duct.
Example
A wall-mounted canopy hood of 12 ft is over medium-duty equipment (ranges, griddles and fryers). The code table gives 300 cfm per foot, so the total exhaust is 12 × 300 = 3,600 cfm. The make-up air is 80% of that, 3,600 × 0.8 = 2,880 cfm. A round duct at 1,500 ft/min needs an area of 3,600 / 1,500 = 2.4 ft², or 345.6 in², which is a diameter of 21.0 in.
Why it matters
The calculator helps restaurant owners, kitchen designers, mechanical engineers, contractors and inspectors to estimate the airflow of a new hood, to size the exhaust fan and the make-up air unit and to prepare the permit. It gives the code starting values before the choice of the listed hood.
Good to know
Use the duty of the hottest appliance under the hood to set the rate for the entire hood. Add to the length of the hood the overhang required on the open sides. Keep the duct velocity within 500 to 2,500 ft/min and respect the clearances and the grease duct rules. Balance the make-up air to keep the kitchen at a slight negative pressure, and check the code adopted locally.
Related tools
The bathroom fan calculator covers small exhaust fans, the air changes calculator covers ventilation rates, the duct size calculator sizes ducts and the HRV installation cost calculator covers heat recovery ventilators.