Needed fire flow calculator: water flow a building needs for fire suppression (ISO method)

Enter the construction class, the floor areas and the occupancy factor to get the effective area, the needed fire flow rounded to 250 gpm, the duration and the water volume.

Updated on
Your inputs
ft²

Value out of range

ft²

Value out of range

Results

Needed fire flow (rounded to 250 gpm)

1,500 gpm

Effective floor area
7,500 ft²
Calculated fire flow
1,559 gpm
Duration required
2 hours
Water volume for the duration
180,000 gal

The needed fire flow calculator gives the water flow that a building needs for fire suppression with the ISO formula F = 18 C √A, from the construction class, the floor areas and the occupancy, with the duration and the volume of water to supply.

How the calculation works

  • Choose the construction class coefficient C of the building: wood frame, joisted masonry, non-combustible or fire-resistive.
  • Enter the area of the largest floor and the total area of the other floors, which count at 50% in the effective area.
  • Choose the occupancy factor for the combustibility of the contents.
  • The calculator applies the ISO formula F = 18 C √A, adjusts it for the occupancy, rounds it to 250 gpm and gives the duration and the volume of water.

Example

A building of joisted masonry (C = 1.0) has a largest floor of 5,000 ft² and other floors totaling 5,000 ft². The effective area is 5,000 + 0.5 × 5,000 = 7,500 ft². The flow is 18 × 1.0 × √7,500 × 1.00 = 1,559 gpm, which rounds to 1,500 gpm (the nearest 250). The duration is 2 hours (flows up to 2,500 gpm), so the volume of water is 1,500 × 2 × 60 = 180,000 gal.

Why it matters

The calculator helps civil and fire protection engineers, developers, planners and fire officers to estimate the fire flow required for a new building or a subdivision, to size the water supply and the storage and to compare the effect of the type of construction. It gives the starting number for the check of hydrants and mains.

Good to know

Use the construction class by the structure of the building, and the largest area of fire. Add the exposure surcharges of the method if buildings are close, and take into account the credit for sprinklers if your authority allows it. Verify the result against the local fire code and the water utility, and check that the system can deliver the flow at the residual pressure of 20 psi.

The friction loss calculator checks the pressure losses in the mains, the tank volume calculator sizes storage, the pump power calculator sizes fire pumps and the pipe flow velocity calculator checks velocities.

Frequently asked questions

What is the needed fire flow?

The needed fire flow is the rate of water supply that a fire department needs to control a fire in a building, at the fire location, for a given duration. It is used by fire insurance rating organizations and by water utilities to size the hydrants, the mains and the storage of a water system, and by designers to check that the supply of a project is enough.

How does the ISO formula work?

The ISO formula is NFF = 18 C √A, with the flow in gpm, the coefficient C of the type of construction, and the effective area A in ft², which is the area of the largest floor plus 50% of the other floors in this simplified form. The flow is then adjusted by a factor for the occupancy and by increases for the exposure to neighboring buildings, and rounded to the nearest 250 gpm, with a minimum of 500 and a maximum of 8,000 gpm.

How long must the flow be supplied?

The duration depends on the flow: 2 hours for flows of 2,500 gpm or less, 3 hours for 3,000 and 3,500 gpm, and 4 hours above. The total volume of water is the flow times the duration, and it must be available from hydrants, tanks or other sources. Sprinklers reduce the needed flow substantially in many jurisdictions, and the fire code gives its own tables.

What are the limits of the calculator?

The calculator gives the basic ISO flow, without the increases for exposures and communications, and without the reductions for automatic sprinkler systems. Fire codes, such as the International Fire Code Appendix B, give their own tables of fire flow by type of construction and area. The result is a planning figure, and the fire protection engineer and the local authority decide the requirement.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.