The occupant load and egress width calculator gives the occupant load of a space from its floor area and its use in the IBC, the minimum number of exits and the egress width required for doors and stairs.
How the calculation works
- Enter the floor area of the room or space.
- Choose the use of the space, which sets the floor area allowed per occupant in IBC Table 1004.5 (net or gross area).
- The calculator finds the occupant load by dividing the area by the area per occupant, rounded up.
- It gives the minimum number of exits, the total egress width for doors and stairs at 0.2 and 0.3 in per person, and the width of each exit.
Example
A tables-and-chairs assembly room of 3,050 ft² uses 15 ft² net per person. The occupant load is 3,050 / 15 = 203.3, rounded up to 204 people. That needs 2 exits (50 to 500 people). The total width of doors is 204 × 0.2 = 40.8 in, and for stairs 204 × 0.3 = 61.2 in. Divided between two exits, each door would need 20.4 in, so the minimum of 32 in governs.
Why it matters
The calculator helps architects, building owners, tenants, contractors and fire officials to estimate how many people a room can hold, to plan the exits of a restaurant, a classroom, an office or a shop and to check a floor plan early in the design. It gives the numbers for the first check of the egress, before the review by the authority.
Good to know
Use the area and the use of the specific space, and check the net or gross rule of the table. When a space has several uses, calculate each one separately. Confirm the version of the code adopted locally, because the values change between editions and states. Check also the travel distance, the exit separation and the accessibility, and ask the building department for the final approval.