The parallel pipe flow split and equivalent diameter calculator gives the flow in each pipe, the common head loss, the velocity in each pipe and the equivalent single pipe diameter for two pipes in parallel, from the total flow and the diameter, the length and the Hazen-Williams C of each pipe.
How the calculation works
- Enter the total flow that goes to the two pipes.
- Enter the diameter, the length and the Hazen-Williams C of each pipe.
- The calculator finds the flow in each pipe, the common head loss, the velocities and the equivalent single pipe.
Example
A flow of 1,500 gpm splits between a 10 in pipe of 1,000 ft and an 8 in pipe of 1,200 ft, both with C = 120. The two pipes have the same head loss, so the flow splits into 997 gpm and 503 gpm. The head loss is 7.09 ft, and the velocities are 4.07 ft/s and 3.21 ft/s. One pipe of the same length as pipe 1 would need a diameter of 11.68 in to carry the total flow with the same head loss.
Why it matters
The calculator helps water and fire protection engineers, plumbing designers, contractors and students to see how the flow divides in a loop, to check the velocity in each branch, and to replace two pipes in parallel by a single pipe in a first design.
Good to know
Check that the velocity in each pipe stays under the usual limit of the project, often 10 ft/s for water, and add the losses of the valves and of the fittings of each branch. Use the C of the real material and age of the pipes. For a long loop with several branches, make a complete network analysis.
Related tools
The pipe flow velocity calculator gives the velocity in a pipe, the pipe volume calculator gives the volume of water in a line, the water hammer calculator gives the pressure surge when a valve closes and the culvert pipe size calculator sizes a culvert.