Skip to content
Omnikalc

Pipe support spacing calculator: how far apart pipe supports can be

Enter the diameter, the wall thickness, the contents and the extra weight of a steel pipe to get the weight per foot, the span for bending stress, the span for deflection and the recommended maximum spacing of the supports.

Updated on
Your inputs
in

Value out of range

in

Value out of range

Value out of range

lb/ft

Value out of range

psi

Value out of range

in

Value out of range

Results

Recommended maximum support spacing

10.89 ft

Weight of the empty pipe
3.66 lb/ft
Weight of the contents
1.45 lb/ft
Total weight per length
6.11 lb/ft
Span limited by bending stress
11.86 ft
Span limited by deflection
10.89 ft

A pipe between two supports acts like a beam. The pipe support spacing calculator gives the weight per foot of a steel pipe with its contents and insulation, the span allowed by the bending stress and by the deflection, and the recommended maximum spacing of the supports.

How the calculation works

  • Enter the outside diameter and the wall thickness of the steel pipe, for example 2.375 in and 0.154 in for a 2 in schedule 40 pipe.
  • Enter the specific gravity of the contents (1.0 for water, 0 for an empty or gas line) and the extra weight per foot of the insulation, the valves and the fittings.
  • Enter the allowable bending stress (2,300 psi is a common value for the sustained load) and the allowable deflection between supports, such as 0.1 in.
  • The calculator computes the weight per foot, then the span limited by bending, √(8 S Z / w), and the span limited by deflection, (384 E I δ / 5w)^¼. The recommended spacing is the smaller of the two.

Example

A 2.375 in pipe with a 0.154 in wall has a section modulus of 0.561 in³ and a moment of inertia of 0.666 in⁴. The pipe weighs 3.66 lb/ft and the water 1.45 lb/ft. With 1 lb/ft of insulation, the total is 6.11 lb/ft. For 2,300 psi of stress, the span is 11.9 ft. For a deflection of 0.1 in, the span is 10.9 ft. The deflection governs, so the support spacing is 10.9 ft.

Why it matters

The calculator helps plumbers, pipefitters, designers and students to place the hangers and supports of a horizontal pipe, to check the effect of a heavier fluid or of insulation, and to see which of the stress or the deflection governs. It gives a result that is close to the tables, for any diameter and any wall.

Good to know

Use the real wall thickness and add the weight of the insulation, the valves and the traces. For pipes that carry heavy fluids or that are filled for hydrotesting, use a specific gravity of 1 or more. Reduce the spacing at valves and elbows. Check the standard of your project and the local code, which can require a smaller spacing.

The beam deflection calculator covers other beams, the moment of inertia calculator gives I for a section, the pipe volume calculator gives the contents of the pipe and the thermal expansion calculator covers the movement of a hot line.

Frequently asked questions

Why is the support spacing limited?

A pipe between two supports behaves like a beam under its own weight, the weight of its contents and of the insulation. If the supports are too far apart, the bending stress gets too high or the pipe sags. A sag in a drain line can hold water, and in a steam line it can collect condensate. In a hot line, a large sag also adds stress at the joints and at the equipment connections.

What are the two limits of the span?

The first is the bending stress, with a maximum moment of wL²/8 for a simple span, which gives L = √(8 S Z / w). The second is the deflection, with δ = 5 w L⁴ / (384 E I), which gives L = (384 E I δ / 5 w)^¼. The deflection usually governs for small pipes, and the stress for large ones with a thick wall. The smaller of the two spans is the one to use.

Do these values match the standard tables?

The results are close to the tables of the usual piping standards, such as MSS SP-69, which give about 7 ft for 1 in pipe and about 10 ft for 2 in water-filled steel pipe. The tables are rounded and use their own deflection and stress criteria. The result here is for a simple span, which is conservative compared to continuous pipe, and for a straight pipe without concentrated loads.

What are the limits of this calculator?

It applies to steel pipe in horizontal runs without concentrated loads. Put a support near each valve, fitting or change of direction, and not more than a third of the span from an elbow. It does not include the thermal stress, the seismic loads, the wind or the dynamic loads, and plastic or copper pipes have different tables because their stiffness is lower.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.