Gas pipe sizing calculator: capacity of a natural gas or propane pipe

Enter the pipe diameter and length, the allowed pressure drop, the gas type and the load of the appliances to get the pipe capacity in ft³/h and Btu/h, the required flow and the margin of the pipe.

Updated on
Your inputs
in

Value out of range

ft

Value out of range

in w.c.

Value out of range

Btu/h

Value out of range

Results

Capacity divided by the load

1.46

Adequate capacity with a margin
Pipe capacity
145.7 ft³/h
Pipe capacity in heat
145,717 Btu/h
Required flow of gas
100.0 ft³/h

A gas pipe that is too small starves the appliances at peak load. The gas pipe sizing calculator applies the low-pressure equation of the International Fuel Gas Code to give the capacity of a pipe for natural gas or propane, the required flow of the appliances and the margin of the pipe.

How the calculation works

  • Enter the inside diameter of the pipe (0.824 in for 3/4 in schedule 40 steel), the length of the run to the farthest appliance and the pressure drop allowed (0.5 in w.c. is common for low-pressure systems).
  • Enter the total load of the appliances in Btu/h, as the sum of the nameplate inputs, and select the gas: natural gas or propane.
  • The calculator applies the low-pressure equation of the International Fuel Gas Code: Q = 2237 × D^2.623 × (ΔH / (Cr × L))^0.541, with Cr = 0.6094 for natural gas and 1.2462 for propane.
  • It gives the capacity of the pipe in ft³/h and in Btu/h, the required flow and the margin, the capacity divided by the load.

Example

A pipe of 0.824 in inside diameter and 50 ft of length is allowed 0.5 in w.c. of pressure drop, for natural gas. The capacity is 2,237 × 0.824^2.623 × (0.5 / (0.6094 × 50))^0.541 = 145.7 ft³/h, which is 145,700 Btu/h at 1,000 Btu/ft³. The appliances have a total load of 100,000 Btu/h, which needs 100 ft³/h. The margin is 145,717 / 100,000 = 1.46, so the pipe is adequate with room for future appliances.

Why it matters

The calculator helps plumbers, HVAC installers, builders and homeowners to check a gas line before adding a stove, a dryer or a generator, and to compare pipe sizes for a given length. It gives the capacity in the same equation as the code tables, for any diameter and length.

Good to know

Add up the nameplate load of all the appliances, and add the future ones. Use the longest run to the farthest appliance. Keep a margin of at least 20%. Always check the result against the code tables and the rules of the local authority, and have the installation inspected and tested.

The gas line installation cost calculator estimates the price, the propane tank calculator sizes the storage, the boiler size calculator gives the load of a heating appliance and the pipe flow velocity calculator checks the speed in the pipe.

Frequently asked questions

How is a gas pipe sized?

The pipe must carry the total load of the appliances at the farthest point, with a pressure drop low enough for the appliances to work. The low-pressure equation of the International Fuel Gas Code gives the capacity Q in ft³/h for a pipe of diameter D in inches and length L in feet, as Q = 2237 × D^2.623 × (ΔH / (Cr × L))^0.541, where ΔH is the pressure drop in inches of water column and Cr depends on the gas.

What length should I use?

Use the length of the longest run from the meter or the regulator to the farthest appliance, including the equivalent length of the fittings if the longest-length method is used. Codes also allow other methods in which each section is sized with its own length. The sizing tables in the code, by pipe size and length, are based on the same equation, and they are the reference for permits.

What is the difference between natural gas and propane?

Natural gas has about 1,000 Btu/ft³ and a specific gravity of 0.60. Propane has about 2,500 Btu/ft³ and a specific gravity of 1.52. A pipe of the same size carries a lower volume of propane than of natural gas, but each cubic foot has 2.5 times more energy, so the capacity in Btu/h is higher. Propane systems usually have a much higher supply pressure, so check the regulator and the system pressure.

What are the limits of this calculator?

It applies to low-pressure systems of 14 in w.c. or less with the pressure drop given. It does not cover higher-pressure systems, the design of regulators, polyethylene or corrugated tubing, or the effect of the fittings. A permit and a licensed installer are needed for gas work, and the installation must be tested for leaks.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.