Punching shear calculator: will the column punch through the slab?

Enter the column size, the slab depth, the concrete strength and the shear force to get the ACI 318 punching shear strength and the demand ratio.

Updated on
Your inputs
in

Value out of range

in

Value out of range

in

Value out of range

psi

Value out of range

kip

Value out of range

Results

Ratio of Vu to φVc

0.86

The slab resists the punching shear
Critical perimeter b0
90.0 in
Nominal punching shear strength Vc
148.0 kip
Design strength φVc
111.0 kip
Governing coefficient (limit of 4, 2 + 4/β or 2 + αs d/b0)
4.00

Flat slabs rest straight on columns, and the weak point is the slab around each column, which can shear off in a cone. The punching shear calculator takes the column dimensions, the slab effective depth, the concrete strength, the column location and the factored shear force, and gives the critical perimeter, the nominal and design strengths and the ratio of demand to capacity, with the governing coefficient.

How the calculation works

  • Enter the column dimensions, the effective depth of the slab, the concrete strength and the column location.
  • Enter the factored shear force Vu that the column puts into the slab.
  • The calculator finds the critical perimeter b0 at a distance of d/2 from the column and takes the smallest of the three ACI 318 limits: 4, 2 + 4/β and 2 + αs d / b0, with αs = 40, 30 and 20 for interior, edge and corner columns.
  • The nominal strength is Vc = k × √f’c × b0 × d, and the design strength is φVc with φ = 0.75. The ratio Vu / φVc must stay at or below 1.

Example

A 16 in × 16 in interior column bears on a slab with d = 6.5 in and 4,000 psi concrete. The perimeter b0 is 4 × (16 + 6.5) = 90 in. The three limits are 4, 2 + 4/1 = 6 and 2 + 40 × 6.5 / 90 = 4.89, so the coefficient is 4. Vc = 4 × √4,000 × 90 × 6.5 / 1,000 = 148.0 kip and φVc = 111.0 kip. With Vu = 95 kip, the ratio is 0.86, so the slab passes.

Why it matters

Punching shear often decides the thickness of a flat slab or a footing, more than bending does. A quick check shows how much margin a design has, how much depth you would gain from a small change, and whether a column added later, such as a bigger load from an extra floor, needs shear reinforcement.

Good to know

The calculator covers slabs without shear reinforcement and without moment transfer, which would add a shear stress that grows with the unbalanced moment. It ignores openings near the column, prestressing and lightweight concrete. The perimeter for edge and corner columns assumes the slab edge is flush with the column face. Real designs need the full ACI 318 check by an engineer.

The footing size calculator sizes spread footings, which also need a punching check, the concrete volume calculator sizes the pour, the rebar calculator counts the steel, and the beam deflection calculator checks bending.

Frequently asked questions

What is punching shear?

It is a failure of a flat slab or a footing in which a column pushes through the slab along a cone or pyramid-shaped surface. It is sudden, with little warning, and can spread from one column to its neighbours and bring down a whole floor. This is why codes check it for every slab column and every spread footing.

Where is the critical section?

ACI 318 places it at a distance of d/2 from the face of the column, around its full perimeter. For an interior column, that is a square or rectangle with sides c + d. For an edge column, the perimeter has three sides, and for a corner column it has two. The slab depth d is measured to the centre of the tension steel.

What increases the punching shear strength?

A deeper slab raises the strength fastest, because d appears in both the perimeter and the area. A larger column, stronger concrete, drop panels, column capitals and shear reinforcement such as studs or stirrups all help. Higher concrete strength helps only with its square root, so it is slow to help.

What do the three coefficients mean?

The limit of 4 applies to compact columns. The 2 + 4/β limit lowers the strength for long rectangular columns, where β is the ratio of the long side to the short side. The 2 + αs d/b0 limit lowers it for columns with a large perimeter, where the critical section is large compared with the slab depth.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.