The raised access floor calculator gives the number of panels, the panels to cut at the edges, the number of pedestals, the panels to order with the waste and the volume of the plenum under the floor, from the size of the room, the size of the panels and the height of the floor.
How the calculation works
- Enter the length and the width of the room and the size of the panels.
- Enter the height of the floor above the slab and the waste and spare panels.
- The calculator finds the panels, the panels to cut, the pedestals, the panels to order and the volume of the plenum.
Example
A room of 42 ft by 31 ft with panels of 2 ft needs 21 panels by 16, that is 336 panels. Of these, 21 are cut at the edge of the room, because 31 ft is not a multiple of 2 ft. The grid needs 22 × 17 = 374 pedestals. With 5 % of spare panels, the order is 353 panels. A floor 12 in high makes a plenum of 42 × 31 × 1 = 1,302 ft³.
Why it matters
The calculator helps data center designers, contractors, facility managers, estimators and students to count the panels and the pedestals of a raised floor, to order the right quantity with spare panels, and to estimate the volume of the plenum that carries the cables and the cold air.
Good to know
Check the flatness of the slab and seal it before the pedestals are set, because dust under the floor harms the equipment. Start the grid from the centre or from a reference line so that the cut panels at the edges are the same on both sides. Keep spare panels of the same batch for later repairs, and check the rating of the panels against the weight of the heaviest rack.