Refrigeration COP calculator: how much power a cooling cycle needs

Enter the evaporating and condensing temperatures, the cooling capacity and the second-law efficiency of a refrigeration cycle to get the Carnot COP, the real COP, the compressor power, the EER and the heat rejected.

Updated on
Your inputs
°F

Value out of range

°F

Value out of range

tons

Value out of range

%

Value out of range

Results

Real COP of the cycle

3.30

Typical for an air-conditioning or chiller cycle
Carnot COP Te / (Tc − Te)
6.00
Compressor power
5.33 kW
Energy efficiency ratio EER
11.25 Btu/Wh
Heat rejected at the condenser
22.92 kW

The COP of a refrigeration cycle tells how much cooling comes from each unit of compressor work. The refrigeration COP calculator finds the Carnot COP for the evaporating and condensing temperatures, the real COP with the second-law efficiency, the compressor power, the EER and the heat rejected at the condenser.

How the calculation works

  • Enter the evaporating and condensing temperatures of the refrigeration cycle and the cooling capacity in tons of refrigeration (1 ton = 12,000 Btu/h).
  • Enter the second-law efficiency, the share of the ideal Carnot COP that the real cycle achieves: about 45% to 60% for a good compressor and cycle, and up to 70% for the best large chillers.
  • The calculator computes the Carnot COP = Te / (Tc − Te), with the absolute temperatures, which is the upper limit of a refrigerator working between these temperatures.
  • It multiplies it by the efficiency to get the real COP, then gives the compressor power needed, the EER and the heat rejected at the condenser.

Example

A refrigeration plant works with an evaporating temperature of 20 °F (266.5 K) and a condensing temperature of 100 °F (310.9 K), and a capacity of 5 tons (17.58 kW). The Carnot COP is 266.5 / (310.9 − 266.5) = 6.00. With a second-law efficiency of 55%, the real COP is 3.30. The compressor power is 17.58 / 3.30 = 5.33 kW, the EER is 3.30 × 3.412 = 11.25 Btu/Wh and the condenser rejects 17.58 + 5.33 = 22.92 kW.

Why it matters

The calculator helps refrigeration technicians, HVAC and cold storage designers, food plant engineers and students to estimate the power of a compressor, to compare the effect of temperatures on the energy use, and to see the gain of a lower condensing temperature. It also gives the heat that the condenser must reject.

Good to know

Use the saturated refrigerant temperatures at the suction and discharge pressures. Keep the condensing temperature as low as the ambient allows. Compare the result with the compressor data at the same conditions. Remember that the evaporating temperature sets the coldest temperature the plant can maintain.

The Carnot efficiency calculator covers engines, the heat pump balance point calculator covers heating with a heat pump, the heat pump cost calculator estimates the running cost and the heat loss calculator gives the load to remove.

Frequently asked questions

What is the COP of a refrigeration cycle?

The coefficient of performance (COP) is the ratio of the heat removed from the cold space to the electrical work of the compressor. A COP of 3 means that 3 kW of cooling comes from 1 kW of electricity. Unlike the efficiency of an engine, the COP is greater than 1, because the machine moves heat, it does not make it. The EER is the same ratio with the capacity in Btu/h and the power in watts.

What is the Carnot COP?

The Carnot COP, Te / (Tc − Te) with absolute temperatures, is the highest possible for a refrigerator that works between an evaporator at Te and a condenser at Tc. It depends only on the temperature lift Tc − Te: the smaller the lift, the higher the COP. Real cycles reach 40% to 70% of it because of the throttling loss, the compressor inefficiency, the pressure drops and the temperature differences in the heat exchangers.

How can the COP be raised?

The most effective way is to reduce the temperature lift: raise the evaporating temperature with a larger evaporator or a warmer load, and lower the condensing temperature with a larger or cleaner condenser, a cooler ambient or a variable-speed fan. A 1 °C reduction of the lift raises the COP by about 2% to 3%. Subcooling the liquid and an efficient compressor also help.

What are the limits of this calculator?

It uses the temperatures of the refrigerant, not the air or water temperatures, which differ by 5 to 15 degrees through the exchangers. The second-law efficiency is a single number that hides the details of the refrigerant, the compressor and the cycle. For the exact performance, use the refrigerant properties and the compressor data of the manufacturer. The result is an estimate for comparing options.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.