Heat pump balance point calculator: balance temperature and backup heat

Enter the building load at the design temperature and the capacity of the heat pump at two outdoor temperatures to get the balance point, the capacity at the design temperature and the backup heat needed.

Updated on
Your inputs
Btu/h

Value out of range

°F

Value out of range

°F

Value out of range

Btu/h

Value out of range

Btu/h

Value out of range

Results

Balance point temperature

22.6 °F

Low balance point: the heat pump carries most of the season
Heat loss coefficient of the building
553.8 Btu/h·°F
Heat pump capacity at the design temperature
19,200 Btu/h
Backup heat needed at the design temperature
16,800 Btu/h
Backup heat needed at the design temperature
4.92 kW
Share of the load met by the heat pump at the design temperature
53.3 %

A heat pump loses capacity as it gets colder, while the house needs more heat. The heat pump balance point calculator gives the outdoor temperature where the two meet, the capacity at the design temperature, the backup heat needed and the share of the load that the heat pump covers.

How the calculation works

  • Enter the heating load of the building at the outdoor design temperature, from a load calculation, and the indoor temperature of the thermostat.
  • Enter the capacity of the heat pump at 47 °F and at 17 °F, from the manufacturer’s performance data. The calculator draws a straight line between these two points.
  • The building load is a line that rises as the outdoor temperature falls, and the heat pump capacity is a line that falls as it gets colder. They cross at the balance point.
  • The calculator gives the heat loss coefficient, the balance point, the heat pump capacity at the design temperature and the backup heat needed there, with the share of the load that the heat pump covers.

Example

A house has a load of 36,000 Btu/h at 5 °F and 70 °F indoors, so the heat loss coefficient is 36,000 / 65 = 553.8 Btu/h·°F. A heat pump delivers 36,000 Btu/h at 47 °F and 24,000 Btu/h at 17 °F, which is a loss of 400 Btu/h per degree. The two lines cross at 22.6 °F: below this temperature, the heat pump cannot meet the load alone. At the design temperature, the heat pump gives 19,200 Btu/h, 53% of the load, and the backup heat must provide 16,800 Btu/h, or 4.92 kW.

Why it matters

The calculator helps homeowners, HVAC designers, energy auditors and students to size a heat pump and its backup, to compare models by their low-temperature capacity and to understand why the heating bill depends on the balance point. It makes the interaction of the load and the capacity visible.

Good to know

Use the capacity data at low temperature from the manufacturer, not the nominal value. Use a load calculation, not the size of the old furnace. Plan the control so that the backup heat comes on only below the balance point. Improving the insulation or the air tightness lowers the load line and the balance point.

The heat pump cost calculator estimates the price, the geothermal heat pump cost calculator covers the ground source, the heat loss calculator gives the load of the building and the heating degree days calculator estimates the season.

Frequently asked questions

What is the balance point of a heat pump?

The balance point is the outdoor temperature at which the heat pump capacity is equal to the heat loss of the building. Above it, the heat pump has more capacity than the house needs, and it cycles on and off. Below it, the heat pump runs all the time and still falls short, so a backup heat source, such as electric strips or a furnace, has to make up the difference.

What balance point is good?

A lower balance point means that the heat pump covers more of the winter. For a cold-climate design, a balance point 10 °F to 20 °F above the design temperature is common, and a cold-climate heat pump with good output at low temperatures can have a balance point below the design temperature, which means no backup. A balance point above 35 °F means a small heat pump for the house, or a building with a high heat loss.

How should I size the heat pump?

Size the unit for the cooling load in a hot climate, where the heat pump will be oversized for heating anyway, and for the heating load in a cold climate with a cold-climate model. In a mixed climate, a balance point of 25 °F to 30 °F is a typical compromise. Use the capacity data of the manufacturer at the temperatures of the design, and not the rated capacity at 47 °F.

What are the limits of this calculator?

It uses straight lines for the load and for the capacity, which is a good approximation for a typical single-speed or two-stage unit, but not for a variable-speed one with a capacity that is flat or that has steps. It does not include the defrost cycles, the minimum operating temperature of the unit, the change of efficiency or the solar and internal gains that lower the balance point of a real house.