Skip to content
Omnikalc

Room lighting lumen method calculator

Enter the size of the room, the target illuminance and the data of the fixtures to get the number of fixtures, the illuminance, the power density and the spacing.

Updated on
Your inputs
ft

Value out of range

ft

Value out of range

fc

Value out of range

lm

Value out of range

Value out of range

Value out of range

W

Value out of range

Results

Number of fixtures

12

Fixtures needed, exact value
11.1
Illuminance with that number
54.0 fc
Lighting power density
1.25 W/ft²
High: use fixtures with a better efficacy
Spacing of a square grid
5.66 ft

The room lighting lumen method calculator gives the number of fixtures needed to reach a target illuminance, the illuminance with that number, the lighting power density and the spacing of a square grid, from the size of the room and the data of the fixtures.

How the calculation works

  • Enter the length and the width of the room, and the illuminance you want in footcandles.
  • Enter the light output and the power of one fixture, the coefficient of utilization and the light loss factor.
  • The calculator finds the number of fixtures, the illuminance with that number, the power density and the spacing.

Example

A room of 24 ft by 16 ft has an area of 384 ft². To get 50 fc with fixtures of 3,600 lm, a coefficient of utilization of 0.6 and a light loss factor of 0.8, the room needs 50 × 384 / (3,600 × 0.6 × 0.8) = 11.1, rounded up to 12 fixtures. They give 54.0 fc, use 12 × 40 = 480 W, that is 1.25 W/ft², and fit a square grid with a spacing of 5.66 ft.

Why it matters

The calculator helps electricians, contractors, designers, facility managers and homeowners to size the lighting of an office, a shop, a classroom or a garage, to compare fixtures by their output and their power, and to check the energy use of the layout before they buy.

Good to know

Use the target illuminance of the task and not more: about 30 fc for an office with screens, 50 fc for a classroom, 30 to 50 fc for a workshop and 10 fc for a corridor. Use the data of the manufacturer for the coefficient of utilization. Place the fixtures on a regular grid, with a spacing under the mounting height times the spacing ratio of the fixture, and keep a half spacing at the walls.

The recessed lighting calculator gives the layout of can lights, the lumens calculator converts watts and lumens, the emergency egress lighting calculator gives the spacing of the emergency fixtures and the average daylight factor calculator gives the daylight in a room.

Frequently asked questions

What is the lumen method?

The lumen method estimates the average illuminance on the work plane of a room from the light that the fixtures emit. The number of fixtures is the target illuminance times the area, divided by the lumens of one fixture times the coefficient of utilization and the light loss factor. It gives an average value for a room with a regular layout and does not show the light at a given point.

What is the coefficient of utilization?

The coefficient of utilization is the fraction of the light of the fixtures that reaches the work plane. It depends on the type of fixture, on the reflectance of the ceiling, the walls and the floor, and on the proportions of the room, which are given by the room cavity ratio. A typical value is 0.5 to 0.7 for a bright room, and it can fall to 0.3 for a dark, narrow room.

What is the light loss factor?

The light loss factor takes into account the decrease of the light with time, from the aging of the lamps, the dirt on the fixtures and the room surfaces, and the failure of lamps. A value of 0.8 is common for LED fixtures in a clean room. A lower value is used for a dirty place or for sources that lose their output quickly.

What does the calculator leave out?

The calculator does not include the daylight, the glare, the uniformity, the vertical illuminance or the control of the lights, and the number it gives is an estimate. For a final design, use a photometric file of the fixture and a lighting software, and check the requirements of the code for the type of room, in footcandles and in watts per square foot.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.