The sprinkler system demand calculator gives the water flow of a sprinkler design area from the design density, the area of operation, the coverage per sprinkler and the K-factor, with the pressure at a sprinkler and the total demand including the hose stream allowance.
How the calculation works
- Enter the design density (gpm per ft²) and the design area of operation from the hazard classification of NFPA 13.
- Enter the coverage area of one sprinkler, which is limited by the hazard (up to 130 ft² for ordinary hazard) and the K-factor of the sprinkler.
- Choose the hose stream allowance for the hazard.
- The calculator finds the sprinkler demand (density × area), the number of sprinklers, the flow and pressure at each one, and the total demand with the hose stream.
Example
An ordinary hazard (Group 1) system has a density of 0.15 gpm/ft² over a design area of 1,500 ft², with 130 ft² per sprinkler of K = 5.6 and a hose allowance of 250 gpm. The sprinkler demand is 0.15 × 1,500 = 225 gpm, with 1,500 / 130 → 12 sprinklers. Each one flows 0.15 × 130 = 19.5 gpm, at a pressure of (19.5 / 5.6)² = 12.1 psi. The total demand is 225 + 250 = 475 gpm.
Why it matters
The calculator helps fire protection engineers, sprinkler contractors, building designers and students to estimate the water demand of a sprinkler system for a building, to size the supply, the pump and the tank in a first design and to compare different hazards. It reproduces the first step of a hydraulic calculation.
Good to know
Take the density and the area from NFPA 13 for the exact occupancy classification and the sprinkler type, and remember that the hazard of a storage area can be much higher than the one of the offices. Add the friction losses and the elevation to the pressure. Check the water supply with a flow test. Only a licensed professional can design and certify the sprinkler system.
Related tools
The friction loss calculator gives the pressure losses in the pipes, the pump power calculator sizes the fire pump, the tank volume calculator sizes the storage and the pipe flow velocity calculator checks the velocities.