Stack effect calculator: draft pressure and airflow from height and temperature

Enter the height of a chimney or a building and the indoor and outdoor temperatures to get the stack effect pressure difference in inches of water and pascals, with the velocity and airflow through an opening.

Updated on
Your inputs
ft

Value out of range

°F

Value out of range

°F

Value out of range

ft²

Value out of range

Results

Stack effect pressure difference

0.0450 in w.c.

Stack effect pressure difference
11.2 Pa
Air velocity through the opening
8.77 ft/s
Airflow through the opening
526 CFM

Warm air rises, and the pressure that it creates is the stack effect. The stack effect calculator gives the pressure difference of a chimney or a building from the height and the temperatures, and the velocity and the airflow that this pressure drives through an opening.

How the calculation works

  • Enter the height of the column of warm air: the height of a chimney, or the distance between the neutral pressure plane and the opening in a building.
  • Enter the outdoor air temperature and the indoor temperature (or the average temperature of the flue gas in a chimney).
  • Enter the area of the opening to estimate the airflow driven by the stack effect, for a door, a leak or a vent.
  • The calculator applies ΔP = 3,462 × h × (1/To − 1/Ti) in pascals, with h in meters and the temperatures in kelvin, then the velocity 0.65 √(2 g h ΔT / T).

Example

A heated space has a column of warm air of 30 ft (9.14 m), with 20 °F outside and 70 °F inside. In kelvin, that is 266.5 K and 294.3 K. The pressure difference is ΔP = 3,462 × 9.14 × (1/266.5 − 1/294.3) = 11.2 Pa, or 0.0450 in w.c. The velocity through an opening is 0.65 × √(2 × 9.81 × 9.14 × 27.8 / 294.3) = 8.77 ft/s, so a 1 ft² opening passes 526 CFM.

Why it matters

The calculator helps builders, HVAC technicians, energy auditors and students to see why a chimney draws, why a tall building leaks air in winter and how much the temperature and the height matter. It is a quick check before a more detailed airflow analysis.

Good to know

Use the average temperature of the gas in the chimney, which is lower than the temperature at the appliance. Remember that the pressure doubles when the height doubles, and that it grows with the temperature difference. Seal the top and the bottom of the building to reduce the stack leakage, and check the combustion air supply of the appliances.

The chimney height calculator gives the 3-2-10 rule, the air changes calculator converts the airflow to a ventilation rate, the wind load calculator covers the other natural pressure and the attic ventilation calculator sizes the vents.

Frequently asked questions

What is the stack effect?

The stack effect, or chimney effect, is the movement of air caused by the difference of density between warm and cold air. The warm air is lighter and rises, and the colder air comes in at the bottom. In a chimney, it creates the draft that carries the flue gas out. In a tall building, it pulls air in at the bottom and pushes it out at the top in winter, which affects the heating, the doors and the elevators.

How is the pressure difference computed?

The pressure difference over a height h is ΔP = ρo g h (To − Ti) / Ti, which can be written ΔP = 3,462 × h × (1/To − 1/Ti) in pascals, with h in meters and the absolute temperatures in kelvin. It increases linearly with the height and with the temperature difference. In a building, h is the distance from the neutral pressure plane, where the indoor and outdoor pressures are equal, to the opening.

How much draft does a chimney need?

A natural draft appliance usually needs a draft of 0.02 to 0.06 in w.c. (5 to 15 Pa) at the base of the chimney to carry the flue gas out safely. A taller chimney or a hotter flue gas raises the draft. A cold chimney, or a house that is under negative pressure because of exhaust fans, can have too little draft, which can cause backdrafting.

What are the limits of this calculator?

It gives the theoretical pressure difference for a column at uniform temperature. A real chimney loses the heat of the gas as it rises, so the average temperature is lower than the entering temperature, and the friction in the flue reduces the draft. In a building, the position of the neutral plane, the leaks and the mechanical systems change the result. Use it for a first estimate.