Wet well volume calculator: size a lift station or sump for the pump cycle time

Enter the pump capacity, the minimum cycle time and the diameter of a wet well to get the working volume between the start and stop levels, the working depth and the maximum number of starts per hour.

Updated on
Your inputs
gpm

Value out of range

min

Value out of range

ft

Value out of range

Results

Working depth between pump on and off

3.55 ft

Required working volume
750 gal
Required working volume
100.3 ft³
Maximum pump starts per hour
6.0

A wet well needs enough working volume so that its pump does not start too often. The wet well volume calculator applies the rule V = Q × T / 4 to give the working volume, the working depth for a given diameter and the maximum number of starts per hour.

How the calculation works

  • Enter the capacity of the pump at its operating point, in gallons per minute, and the minimum cycle time: the shortest time between two starts of the same pump, which is 10 minutes for a motor with 6 starts per hour (the motor manufacturer gives the limit).
  • Enter the inside diameter of the wet well or the sump.
  • The calculator applies the classic rule V = Q × T / 4, which comes from the worst case for the number of starts: an inflow equal to half of the pump capacity.
  • It gives the working volume between the start level and the stop level, the working depth for the diameter that you chose and the maximum number of starts per hour.

Example

A pump of 300 gpm has a minimum cycle time of 10 minutes, which is a maximum of 6 starts per hour. The working volume is 300 × 10 / 4 = 750 gal, or 100.3 ft³. In a wet well of 6 ft of diameter (28.3 ft² of area), the working depth between the start and the stop of the pump is 100.3 / 28.3 = 3.55 ft.

Why it matters

The calculator helps civil and plumbing engineers, contractors, operators of small pump stations and students to size a lift station, a sump or an effluent pit. It also shows why a larger pump needs a larger well for the same cycle time.

Good to know

Use the real operating point of the pump, not the nameplate flow. Use the cycle time of the motor manufacturer. Add the volume below the stop level for the submergence of the pump and the freeboard above the start level. For a very long retention time, check the odor and the sludge.

The pump power calculator gives the power of the pump, the tank volume calculator gives the volume of a tank of a given size, the sump pump calculator sizes basement pumps and the tank drain time calculator gives the time to empty a tank.

Frequently asked questions

What is the working volume of a wet well?

A wet well, or a lift station, collects the flow of a sewer or a drain and a pump empties it from time to time. The working volume is the volume between the level where the pump starts and the level where it stops. If this volume is too small, the pump starts too often and the motor overheats. If it is too big, the sewage stays too long in the well and can turn septic and smell.

Where does V = Q T / 4 come from?

The time between starts is the sum of the time to fill and the time to empty. With an inflow q and a pump capacity Q, the cycle is T = V/q + V/(Q − q). It is the shortest when q = Q/2, and then T = 4V/Q. So the volume that keeps the cycle at or above T in the worst case is V = Q × T / 4. For other inflows, the cycle is longer.

What cycle time should I use?

The limit depends on the motor, and the manufacturer gives the maximum number of starts per hour. Small motors of a few horsepower can start 10 to 15 times per hour, motors from 10 to 100 hp are limited to about 6 per hour, and large motors can be limited to 3 or fewer. Many standards also ask for a maximum retention time of 30 minutes in the well.

What are the limits of this calculator?

It gives the working volume only. The total depth of a wet well also includes the volume below the stop level to keep the pump submerged, the freeboard above the alarm level, the space for the inlet pipe and the storage for emergencies. Variable speed pumps need much less volume. Follow the design standard of the utility, and check the minimum submergence of the pump.