Skip to content
Omnikalc

Window solar heat gain calculator: solar gain through a window and cooling load

Enter the window area, the SHGC, the solar irradiance, the shaded share and the hours of sun to get the solar heat gain, the gain per area, the cooling equivalent and the saving from a lower-SHGC glass.

Updated on
Your inputs
ft²

Value out of range

Value out of range

Btu/h·ft²

Value out of range

%

Value out of range

h

Value out of range

Value out of range

Results

Solar heat gain through the window

2,560 Btu/h

Solar heat gain per area of window
64.0 Btu/h·ft²
Moderate solar gain per area
Cooling load equivalent of the gain
0.213 tons
Daily solar energy entering
4.50 kWh/day
Reduction in the gain with the alternative glass
960 Btu/h

The window solar heat gain calculator gives the heat that enters through a window from its area, its SHGC, the solar irradiance and the shading, and shows the gain per area, the cooling equivalent, the daily energy and the saving from a glass with a lower SHGC.

How the calculation works

  • Enter the window area, the SHGC of the glass from the label and the solar irradiance on the window at the design hour.
  • Enter the share of the window that is shaded by an overhang, a screen or a blind, and the equivalent hours of full sun per day.
  • The calculator finds the solar heat gain Q = A × SHGC × irradiance × (1 − shaded share).
  • It gives the gain per area, its cooling equivalent in tons, the daily energy and the reduction with an alternative glass.

Example

A window of 40 ft² with an SHGC of 0.40 receives 200 Btu/h·ft² and 20% of it is shaded. The solar heat gain is 40 × 0.40 × 200 × 0.80 = 2,560 Btu/h, which is 64.0 Btu/h per ft² and 0.213 tons of cooling. Over 6 hours of full sun it brings 4.50 kWh per day. With a glass of SHGC 0.25, the gain falls by 40 × 0.15 × 200 × 0.80 = 960 Btu/h.

Why it matters

The calculator helps homeowners, architects, HVAC designers and builders to see how much a window adds to the cooling load, to compare glass types and to judge whether shading or a film is worth the cost. It gives the weight of the windows in the summer heat before a full cooling load calculation.

Good to know

Use the SHGC of the complete window, from the label, and the irradiance for the orientation and the hour that drives the peak load. For a daily energy, use the peak sun hours of the site and do not forget that the shading changes during the day. Consider the effect on winter heating and on daylight before choosing a low-SHGC glass, and use a full load calculation to size the equipment.

The window area calculator checks the glazing area, the window film calculator covers retrofit films, the heat loss calculator covers heating and the solar panel tilt calculator helps with the sun angle.

Frequently asked questions

What is the solar heat gain coefficient?

The SHGC is the fraction of the incident solar radiation that enters through the window as heat, both directly transmitted and absorbed then released inward. It goes from 0 to 1 and is on the NFRC label of the window. A low SHGC of 0.25 or less is good for hot climates and a high SHGC of 0.4 or more is useful in cold climates, where the sun helps to heat the house in winter.

What irradiance should I use?

The peak irradiance on a vertical window depends on the orientation and the season. For a clear day, a south-facing window receives about 100 to 200 Btu/h·ft² (300 to 600 W/m²) in summer at midday, and less in the morning and afternoon. East and west windows receive their peak of 200 to 250 Btu/h·ft² in the morning or the afternoon. The cooling load calculation uses tables by orientation and latitude.

How can I reduce solar gain?

The best option is outside shading, such as an overhang, an awning, shutters or trees, which stops the sun before the glass. Interior blinds work less well, because the heat is already inside. Low-emissivity glass with a low SHGC, tinted glass and reflective films also reduce the gain, but they cut the winter sun and the daylight too, so the orientation must be considered.

How is this used in the cooling load?

The solar gain through the windows is often the largest part of the cooling load of a room. The cooling load calculation adds it to the conduction through the glass, the people, the lights and the equipment, and applies a factor for the storage of heat in the room. The tons shown here are the instant equivalent of the solar gain only, 12,000 Btu/h per ton.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.