Motor starting current calculator: inrush current by starting method

Enter the power, the voltage, the efficiency, the power factor and the locked-rotor multiple of a three-phase motor, and choose the starting method to get the full-load current, the starting current and the starting torque.

Updated on
Your inputs
hp

Value out of range

V

Value out of range

Value out of range

Value out of range

Value out of range

Results

Starting current drawn from the line

65 A

Full-load current
29.9 A
Locked-rotor current (direct on line)
194 A
Starting current as a multiple of full-load current
2.17
Gentle start for the supply
Starting torque compared with direct on line
33 %

A three-phase motor draws many times its normal current for a few seconds when it starts. The motor starting current calculator gives the full-load current, the locked-rotor current, the starting current drawn from the line and the starting torque for a direct, star-delta, autotransformer or soft start.

How the calculation works

  • Enter the rated power, the line voltage, the efficiency and the power factor of the motor, from the nameplate or the datasheet, to get the full-load current.
  • Enter the locked-rotor multiple: the ratio of the starting current to the full-load current with the rotor blocked, which is 6 to 8 for most standard motors (the code letter on the nameplate gives it).
  • Choose the starting method: direct on line, star-delta, autotransformer or soft starter. Each one reduces the voltage on the motor at the start.
  • The calculator gives the full-load current, the locked-rotor current, the starting current drawn from the line and the starting torque, which falls with the square of the voltage.

Example

A 25 hp motor on 460 V has an efficiency of 92%, a power factor of 0.85 and a locked-rotor multiple of 6.5. The full-load current is 18,643 W / (√3 × 460 × 0.91 × 0.85) = 29.9 A, and the locked-rotor current is 194 A. With a star-delta starter, the winding sees 1/√3 of the voltage, and the line current falls to one third, 65 A, which is 2.17 times the full-load current. The starting torque is also one third, 33% of the value for a direct start.

Why it matters

The calculator helps electricians, plant engineers and students to size the supply, the cables and the protection for a motor, to compare the starting methods and to check if a reduced voltage start is needed to limit the voltage dip. It also shows the price in torque of each method.

Good to know

Check that the load can start with the reduced torque. A pump or a fan with a low starting torque is a good candidate for star-delta or a soft starter, and a loaded conveyor or a compressor is not. Do not size the protection on the locked-rotor current alone. Follow the electrical code for the overload and the short-circuit protection of motor circuits.

The motor current calculator gives the current for a given power, the star-delta calculator explains the connection, the power factor correction calculator sizes the capacitors and the wire size and voltage drop calculator checks the supply cable.

Frequently asked questions

Why is the starting current so high?

At standstill, the rotor of an induction motor has no back electromotive force. The only limit to the current is the impedance of the windings, which is low. So the motor draws a locked-rotor current of 5 to 8 times the full-load current for a short time, until it reaches speed and the back EMF builds up. This inrush can cause a voltage dip on the supply, flicker, and the trip of protective devices.

How do the starting methods reduce the current?

All of them lower the voltage at the motor at the start. The current of the motor is proportional to the voltage, and the torque to the square of the voltage. With a star-delta starter, the windings are connected in star, at 58% of the voltage, so the line current and the torque fall to one third. An autotransformer with a 65% tap gives 42% of the current and the torque. A soft starter ramps the voltage, and a setting of 50% gives 50% of the line current and 25% of the torque.

What are the code letters of the nameplate?

In North America, the nameplate of a motor has a code letter that gives the locked-rotor kVA per horsepower. For example, the letter G is 5.6 to 6.3 kVA/hp, which is a multiple of about 6 to 7 at 460 V. Many modern high-efficiency motors have a multiple of 7 to 8. If the nameplate gives the locked-rotor current in amps, divide it by the full-load current to get the multiple.

What are the limits of this calculator?

It gives the steady locked-rotor values. The real current changes during the start, and the star-delta changeover causes a second peak. The calculator also does not include the load torque, which can prevent the motor from accelerating with the low torque of a reduced voltage start, the voltage dip on the cable and the transformer, or the time of the start. Check the torque curves of the motor and of the load.