The motor starting voltage dip calculator gives the starting kVA, the voltage dip at the bus, the bus voltage during the start and the starting torque of a motor, from its size, its locked rotor kVA, the starting method and the short-circuit capacity of the source.
How the calculation works
- Enter the motor rating, the locked rotor kVA per hp of its code letter and the starting method.
- Enter the short-circuit capacity at the motor bus and the system voltage.
- The calculator gives the starting kVA, the voltage dip, the voltage during the start and the starting torque.
Example
A 100 hp motor with 5.8 kVA/hp started direct on line draws 100 × 5.8 = 580 kVA. On a bus of 6,000 kVA of short-circuit capacity the dip is 580 / (580 + 6,000) = 8.8 %. On a 480 V system the bus falls to 437.7 V and the motor torque is (1 − 0.088)² = 83.1 % of its full voltage value.
Why it matters
The calculator helps electrical engineers, contractors, facility engineers and students to check quickly if a large motor can start on a transformer or on a generator without a bad dip, and to compare direct starting with a reduced voltage method.
Good to know
Get the locked rotor kVA per hp from the nameplate or the data sheet, with the code letter, and use the maximum of the range for a check. Take the short-circuit capacity at the motor bus from the study, not at the transformer secondary, if there is a long feeder. For a generator use its subtransient reactance to find the short-circuit kVA, and expect a larger dip than from the utility. Run the check again with the lowest short-circuit capacity that the source can have, for example with the generator alone or with a transformer out of service, since that is the case that gives the largest dip.