Motor starting voltage dip calculator

Enter the motor size, its locked rotor kVA, the starting method and the short-circuit capacity to get the voltage dip at the bus and the starting torque.

Updated on
Your inputs
hp

Value out of range

Value out of range

kVA

Value out of range

V

Value out of range

Results

Voltage dip at the bus

8.8 %

A dip within the usual limit of 10 %
Starting kVA
580 kVA
Voltage at the bus during start
437.7 V
Starting torque as a share of the full voltage torque
83.1 %

The motor starting voltage dip calculator gives the starting kVA, the voltage dip at the bus, the bus voltage during the start and the starting torque of a motor, from its size, its locked rotor kVA, the starting method and the short-circuit capacity of the source.

How the calculation works

  • Enter the motor rating, the locked rotor kVA per hp of its code letter and the starting method.
  • Enter the short-circuit capacity at the motor bus and the system voltage.
  • The calculator gives the starting kVA, the voltage dip, the voltage during the start and the starting torque.

Example

A 100 hp motor with 5.8 kVA/hp started direct on line draws 100 × 5.8 = 580 kVA. On a bus of 6,000 kVA of short-circuit capacity the dip is 580 / (580 + 6,000) = 8.8 %. On a 480 V system the bus falls to 437.7 V and the motor torque is (1 − 0.088)² = 83.1 % of its full voltage value.

Why it matters

The calculator helps electrical engineers, contractors, facility engineers and students to check quickly if a large motor can start on a transformer or on a generator without a bad dip, and to compare direct starting with a reduced voltage method.

Good to know

Get the locked rotor kVA per hp from the nameplate or the data sheet, with the code letter, and use the maximum of the range for a check. Take the short-circuit capacity at the motor bus from the study, not at the transformer secondary, if there is a long feeder. For a generator use its subtransient reactance to find the short-circuit kVA, and expect a larger dip than from the utility. Run the check again with the lowest short-circuit capacity that the source can have, for example with the generator alone or with a transformer out of service, since that is the case that gives the largest dip.

The motor starting current calculator gives the inrush current and the torque, the voltage regulation calculator gives the drop under load, the transformer fault current calculator gives the short-circuit capacity and the generator size calculator sizes a standby set.

Frequently asked questions

How is the voltage dip found?

The dip is estimated by the ratio of the starting kVA of the motor to the sum of this starting kVA and the short-circuit kVA of the source at the motor bus. This is the voltage divider formed by the source impedance and the impedance of the locked motor, and it assumes that the two impedances have the same angle. A stiff source with a high short-circuit capacity gives a small dip, and a weak source such as a generator gives a large one.

What dip is acceptable?

A dip of 10 % at the motor bus is the usual limit, and 15 % is often the maximum, although the limit depends on the other loads. A dip of 3 % or more at a lighting bus can be seen as flicker, and contactors can drop out near 70 to 80 % of the rated voltage. Sensitive loads such as drives and computers may need a lower dip. A utility may also set a limit at the point of supply.

What does a reduced voltage starter do?

A reduced voltage starter lowers the starting current and so the dip, but it lowers the starting torque even more. An autotransformer on the 65 % tap draws about 42 % of the direct kVA and gives 42 % of the torque. A wye-delta starter draws a third of the current and a third of the torque. The motor must still be able to accelerate the load, so check the torque curve.

What does the calculator leave out?

The calculator uses the kVA of the locked rotor and a code letter value, which is a range and not an exact figure, and it does not model the power factor of the start, the change of the dip as the motor accelerates, the cable impedance or the transformer taps. For a real project use a short-circuit and motor starting study, with the data of the motor and of the source.