Will your pump cavitate?

Enter the surface pressure, vapour pressure, liquid density, suction head and losses: get the NPSH available, the margin over the pump's requirement and the safety ratio.

Updated on
Your inputs

Value out of range

Value out of range

kg/m³

Value out of range

Value out of range

Value out of range

Value out of range

Results

NPSH available

11.61 m

Margin over the NPSH required
8.61 m
Ratio NPSHa ÷ NPSHr
3.87
A comfortable margin: cavitation is unlikely

A centrifugal pump pulls liquid in at its inlet, where the pressure is lowest. If it drops below the vapour pressure of the liquid, bubbles form and collapse violently: this is cavitation, which erodes the impeller and wrecks the pump. The test is the NPSH. This calculator gives the NPSH available from your installation and compares it with the NPSH required by the pump.

How the calculation works

  • Pressure head = (surface pressure − vapour pressure) ÷ (density × g)
  • NPSH available = pressure head + static suction head − friction losses
  • Margin = NPSH available − NPSH required
  • Ratio = NPSH available ÷ NPSH required

Example

A pump draws water at 20 °C from an open tank at sea level (101.325 kPa), with a vapour pressure of 2.34 kPa. The liquid level is 2 m above the pump inlet and the suction line loses 0.5 m. The pressure head is 10.11 m, so the NPSH available is 11.61 m. The pump needs 3 m: the margin is 8.61 m and the ratio is 3.87, a very comfortable value.

Where it is used

Choosing and installing a pump starts with this check, especially for hot water, volatile liquids, high altitudes, long suction lines and lifts. If the pump sits above the tank, the static head is negative and the margin shrinks quickly. Heating systems, boiler feed pumps, irrigation pumps and pool pumps all depend on adequate suction conditions.

Good to know

Use absolute pressures, not gauge pressures. The vapour pressure rises quickly with temperature, so a hot liquid has far less margin: water at 80 °C loses 4.9 m of head compared with 20 °C. The NPSH required rises with the flow, so check it at the highest flow you expect. The friction loss is the loss in the suction pipe, valves and strainers, and a clogged strainer can make a good system cavitate.

For the power of the pump, use the pump power calculator. The friction loss calculator gives the losses in the suction pipe, and the hydrostatic pressure calculator the pressure at depth.

Frequently asked questions

What is NPSH?

Net positive suction head: the pressure margin, expressed as a height of liquid, that the liquid has above its vapour pressure at the pump inlet. It must exceed the pump's requirement, or the liquid boils locally and forms bubbles.

What is cavitation?

The formation and collapse of vapour bubbles when the pressure falls below the vapour pressure. It makes noise, damages the impeller and reduces the flow.

How can I increase the NPSH available?

Raise the liquid level or lower the pump, shorten and enlarge the suction pipe, remove fittings, pressurise the tank or cool the liquid to lower its vapour pressure.

What margin should I keep?

A ratio of 1.1 to 1.3 or more, and sometimes a margin of 0.5 to 1 m, is usual. Large pumps and fluids near their boiling point need more.