Transformer voltage regulation calculator: how much does the voltage change under load?

Enter the per-unit resistance and reactance, the power factor and the load to get the voltage regulation, the no-load voltage and the voltage drop of a transformer.

Updated on
Your inputs
%

Value out of range

%

Value out of range

Value out of range

%

Value out of range

V

Value out of range

Results

Voltage regulation

3.164 %

5 % or less: typical for a well-designed transformer
Secondary voltage with no load
495.2 V
Voltage change between no load and load
15.19 V
Approximate regulation (R cos φ + X sin φ)
3.127 %
Largest regulation at this load (power factor matched to the impedance)
4.176 %

A transformer’s voltage dips a little when you load it. The transformer voltage regulation calculator takes the per-unit resistance and reactance, the power factor and type of the load, the load level and the rated voltage, and gives the voltage regulation, the secondary voltage with no load, the voltage change, the approximate regulation and the largest regulation at that load.

How the calculation works

  • Enter the transformer’s resistance and leakage reactance in per unit, as a percentage of its rating. They come from the nameplate or from the short-circuit test.
  • Enter the power factor of the load, whether it is lagging (inductive, such as motors) or leading (capacitive), and the load as a share of the rating.
  • The voltage regulation is the rise in secondary voltage from full load to no load, as a percentage of the loaded voltage: VR = (V no load − V load) ÷ V load.
  • The calculator solves the exact per-unit relation and also shows the common approximation VR ≈ I × (R cos φ ± X sin φ) and the largest regulation the impedance can cause.

Example

A transformer with 1.2 % resistance and 4 % reactance supplies a 480 V load at full load and a 0.85 lagging power factor. The regulation is 3.164 %, so the no-load secondary voltage is 495.2 V and the voltage falls by 15.19 V when the load is connected. The approximation gives 3.127 %, and the largest possible regulation at this load is 4.176 %.

Why it matters

Electrical engineers use voltage regulation to check that equipment sees a steady voltage, to choose tap settings and to compare transformers. It matters most for long feeders, motor loads and sensitive electronics.

Good to know

The calculation uses a simplified series-impedance model and ignores the magnetizing current, which has a small effect on regulation. Impedances change with temperature and tap position, and real systems also have source impedance. Use the nameplate and test data for a specific design.

The transformer calculator covers turns ratio and currents, and the power factor correction calculator shows how to improve the load power factor.

Frequently asked questions

What is voltage regulation?

It is the change in the secondary voltage of a transformer between no load and a given load, expressed as a percentage of the voltage on load. A low value means the voltage stays steady as the load changes. It is caused by the voltage drop across the winding resistance and the leakage reactance.

Why can voltage regulation be negative?

With a leading (capacitive) load, the current through the leakage reactance partly cancels the voltage drop and the secondary voltage can be higher on load than at no load. The regulation is then negative. This is the same effect as the voltage rise on a lightly loaded cable.

How do resistance and reactance affect the result?

The resistance drop is in phase with the current and the reactance drop is 90 degrees ahead. For a lagging load, they both reduce the voltage, and since the reactance is usually larger than the resistance in power transformers, the drop is mostly from the reactance. The calculator solves the exact phasor relation.

What is a typical value?

Distribution transformers usually have a regulation of 2 to 4 % at full load and unity to 0.8 power factor. Lower impedance gives better regulation but a higher short-circuit current, so the designer makes a compromise. Tap changers can compensate for the drop.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.