Transformer short-circuit current calculator: available fault current from kVA, voltage and impedance

Enter the transformer kVA, the secondary voltage, the impedance and the number of phases to get the full-load current and the available fault current at the secondary terminals.

Updated on
Your inputs
kVA

Value out of range

V

Value out of range

%

Value out of range

Results

Available fault current at the secondary terminals

10,459 A

Full-load current
601.4 A
Fault current as a multiple of the full-load current
17.4 ×
Fault power
8.70 MVA
Fault current in kiloamperes
10.46 kA

The available fault current at the secondary of a transformer tells what a short circuit could reach. The transformer fault current calculator gives it from the kVA rating, the voltage and the impedance of the nameplate, with the full-load current, the multiple of it and the fault power in MVA.

How the calculation works

  • Enter the transformer rating in kVA and the secondary voltage in volts (line-to-line for a three-phase transformer).
  • Enter the impedance in percent from the nameplate, and choose three-phase or single-phase.
  • The calculator finds the full-load current I = kVA × 1000 / (√3 × V) for three-phase, or kVA × 1000 / V for single-phase.
  • It divides it by the impedance to give the available fault current at the secondary terminals, the multiple of the full-load current and the fault power in MVA.

Example

A 500 kVA, three-phase transformer with a secondary of 480 V and an impedance of 5.75 % has a full-load current of 500,000 / (1.732 × 480) = 601.4 A. The available fault current is 601.4 / 0.0575 = 10,459 A, that is 17.4 times the full-load current. The fault power is 500 / 0.0575 = 8.70 MVA. The equipment on the secondary must be rated for at least this current.

Why it matters

The calculator helps electricians, electrical engineers and students to check that breakers, fuses and panels have an adequate interrupting rating, to prepare the labels of the equipment and to see the effect of the transformer impedance on the fault level. It is a quick method before a full short-circuit study.

Good to know

The calculation is for a bolted three-phase or single-phase fault at the secondary terminals with an infinite source, and it ignores the impedance of the utility, the cables and the motor contribution. The real values at downstream points are lower. It is not a replacement for a short-circuit study and an arc-flash study made by a qualified engineer following the local electrical code.

The transformer calculator finds the turns ratio and the currents, the power factor correction calculator sizes capacitors, the wire size and voltage drop calculator sizes cables, and the wire ampacity calculator gives the current rating of conductors.

Frequently asked questions

What is the available fault current?

The available fault current is the largest current that flows if a bolted short circuit happens at a point of the system, limited only by the impedances of the supply. At the secondary terminals of a transformer it is a good first estimate of the current that the panels, the breakers and the fuses must be able to interrupt. Equipment must have an interrupting rating at least equal to the available fault current at its location.

How is it computed from the nameplate?

The full-load current is the kVA divided by the voltage (and by √3 for three-phase). The impedance in percent is the voltage that must be applied to the primary to make the full-load current flow in a shorted secondary. So the fault current is the full-load current divided by the impedance in per unit, that is 100 divided by the percent. A transformer with 5 % impedance gives 20 times its full-load current.

Why is this value an upper limit?

The calculation assumes that the utility source is an infinite bus, with no impedance. In reality, the impedance of the source and of the cables between the transformer and the fault reduces the current, so the real value at a distant panel is lower. A full study also includes the contribution of motors. For safety, the transformer value is used as the maximum at the secondary terminals.

Does the result give the arc flash energy?

No. The arc flash incident energy depends on the arcing current, the clearing time of the protection, the distance to the worker and the enclosure, and it is calculated with a method such as IEEE 1584. The fault current is only one input. Studies of short-circuit and of arc flash must be done by a qualified engineer, and the work on live equipment needs the right procedures and equipment.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.