Wire resistance: R = ρL ÷ A

Calculate the resistance of a copper, aluminum or other wire from its gauge or cross-section, its length and its temperature, with the voltage drop and power lost at a given current.

Updated on
Your inputs
Ω·m

Value out of range

Size given as

Value out of range

Value out of range

mm²

Value out of range

Value out of range

°F

Value out of range

A

Value out of range

Results

Resistance of the wire (one way)

0.1588 Ω

Voltage drop over the round trip at this current

4.76 V

Resistance of the round trip (two conductors)
0.3176 Ω
Power lost as heat in the wire
71.5 W
Cross-section
3.309 mm²
Resistance per 1,000 ft
1.588 Ω/1,000 ft

Why wire resistance matters

Every wire turns a little electrical energy into heat. In a short lamp cord the loss is negligible, but in a long run to a shed, a low-voltage lighting circuit or a 12-volt solar system, wire resistance causes voltage drop, dim lights, slow chargers and warm cables. Knowing the resistance helps you pick the right gauge and spot a problem before it becomes a hazard.

The formula

R = ρ × L ÷ A

  • ρ (rho) is the resistivity of the metal, in ohm-meters.
  • L is the length of the conductor.
  • A is the cross-sectional area.

Resistance also changes with temperature: R_T = R₂₀ × (1 + α × (T − 20 °C)), where α is the temperature coefficient.

Resistivity of common conductors at 20 °C

Metal ρ (Ω·m) α (per °C)
Silver 1.59 × 10⁻⁸ 0.0038
Copper (annealed) 1.724 × 10⁻⁸ 0.0039
Gold 2.44 × 10⁻⁸ 0.0034
Aluminum 2.83 × 10⁻⁸ 0.0040
Tungsten 5.6 × 10⁻⁸ 0.0045
Nichrome 1.10 × 10⁻⁶ 0.0004

AWG sizes

The American Wire Gauge diameter is d = 0.127 mm × 92^((36 − AWG) ÷ 39). Every 3 gauges halve or double the area, and every 6 gauges halve or double the diameter. 12 AWG copper is 2.05 mm across (3.31 mm²) and has about 1.59 Ω per 1,000 ft.

Example

A 100-foot run of 12 AWG copper at 68 °F carrying 15 A:

  • One-way resistance: 0.159 Ω
  • Round trip (hot and neutral): 0.318 Ω
  • Voltage drop: 0.318 × 15 = 4.8 V, about 4% of 120 V
  • Heat in the cable: 0.318 × 15² ≈ 72 W

The National Electrical Code recommends keeping voltage drop under about 3% for a branch circuit. Here, upsizing to 10 AWG would bring the drop down to about 3.0 V.

Practical notes

  • Stranded wire has slightly more resistance than solid wire of the same gauge.
  • Wire at its rated operating temperature, such as 167 °F (75 °C), has about 22% more resistance than at room temperature.
  • Connections, terminals and breakers add resistance too; a loose connection can heat up far more than the wire itself.
  • Nichrome is used in heaters and toasters precisely because its high resistivity turns current into heat in a short length.

Frequently asked questions

How is wire resistance calculated?

R = ρ × L ÷ A, where ρ is the resistivity of the metal, L the length and A the cross-sectional area. Doubling the length doubles the resistance; doubling the area halves it. For a circuit, remember the current flows out and back, so the round trip is twice the one-way length.

What is the resistance of 12 AWG copper wire?

About 1.59 ohms per 1,000 feet at 68 °F (20 °C), or 0.16 ohms per 100 feet. 14 AWG is about 2.53 ohms per 1,000 feet and 10 AWG about 1.0. Each step of three gauges roughly doubles or halves the resistance.

How does temperature change resistance?

For most metals, resistance rises with temperature: R = R₂₀ × (1 + α × (T − 20 °C)). For copper, α is about 0.0039 per °C, so a wire at 167 °F (75 °C), a common insulation rating, has about 22% more resistance than at 68 °F.

Why is aluminum wire thicker for the same current?

Aluminum's resistivity is about 64% higher than copper's, so it needs a larger cross-section, typically two AWG sizes larger, for the same resistance and voltage drop. It is lighter and cheaper, which is why utilities use it for service and transmission lines.

Was this calculator helpful?

Thanks for your feedback!