Skip to content
Omnikalc

Arc flash incident energy calculator: heat energy of an electric arc at the working distance

Enter the voltage, the fault current, the arc duration and the working distance to get the incident energy in J/cm² and cal/cm², the PPE category and the arc flash boundary.

Updated on
Your inputs
kV

Value out of range

kA

Value out of range

s

Value out of range

in

Value out of range

Results

Incident energy in calories

4.22 cal/cm²

Incident energy
17.64 J/cm²
Arc flash PPE category (NFPA 70E table)
2
Category 2 or 3: arc-rated clothing, face shield or hood
Arc flash boundary (1.2 cal/cm²)
33.7 in

The arc flash incident energy calculator estimates the thermal energy of an electric arc with the Lee method from the voltage, the fault current, the arc duration and the working distance, with the PPE category of the table of NFPA 70E and the arc flash boundary.

How the calculation works

  • Enter the system voltage in kV, the bolted fault current in kA at the equipment and the arc duration, which is the clearing time of the protective device.
  • Enter the working distance between the worker’s face and chest and the arc, 18 in for a low-voltage panel.
  • The calculator finds the incident energy with the Lee method, in J/cm² and in cal/cm², the PPE category of the table of NFPA 70E and the arc flash boundary at 1.2 cal/cm².

Example

A panel of 480 V (0.48 kV) has a fault current of 30 kA cleared in 0.5 s, with a working distance of 18 in (457 mm). The Lee equation gives E = 512,000 × 0.48 × 30 × 0.5 / 457.2² = 17.64 J/cm², or 4.22 cal/cm². The PPE category is 2, since the energy is between 4 and 8 cal/cm². The boundary at which the energy falls to 1.2 cal/cm² is 18 × √(4.22 / 1.2) = 33.7 in.

Why it matters

The calculator helps electrical engineers, maintenance staff, safety managers and students to understand how the fault current, the clearing time and the distance change the arc flash hazard, and to compare the effect of a faster protective device. It makes the order of magnitude of the hazard clear before the formal study.

Good to know

Use this estimate only to learn and to compare options. Have the arc flash study made by a qualified engineer with the real short-circuit data and the time-current curves of the devices, update it when the system changes, and label the equipment. Always de-energize the equipment when possible and follow the electrical safety program of the site.

The wire ampacity calculator gives the current of a conductor, the conduit fill calculator checks the fill of a conduit, the wire size calculator with voltage drop sizes the conductor and the power factor correction calculator sizes capacitors.

Frequently asked questions

What is the incident energy of an arc flash?

An arc flash is the sudden release of energy by an electric arc between conductors. The incident energy is the thermal energy received on a surface at a given distance, in cal/cm² or J/cm². An energy of 1.2 cal/cm² causes a second-degree burn on bare skin in a fraction of a second. The incident energy is used to choose the arc-rated clothing, as in NFPA 70E, and to label the equipment.

What is the Lee method?

The Lee method is a theoretical approach that computes the incident energy of an arc in open air from the power of the arc, E = 5.12 × 10⁵ V I t / D² in J/cm², with V in kV, I in kA, t in seconds and D in mm. It is simple but conservative for the low voltages and non-conservative for some enclosures. The IEEE 1584 equations are the standard for the arc flash studies in practice, and give a more accurate result.

Why does the clearing time matter so much?

The energy is proportional to the duration of the arc, so the speed of the protective device is the main way to reduce the hazard. A fault cleared in 0.1 s gives one fifth of the energy of a fault cleared in 0.5 s. Current-limiting fuses, zone selective interlocking and an arc flash maintenance mode on the breakers shorten the time, and a working distance greater than 18 in reduces the energy with the square of the distance.

What are the limits of the calculator?

The calculator is an educational estimate. It is not a substitute for an arc flash hazard study according to IEEE 1584 and NFPA 70E, which takes into account the configuration of the electrodes, the enclosure, the gap and the short-circuit calculation of the system, and which must be made by a qualified engineer. Never use this result to choose the protective equipment of a worker.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.