Wire ampacity calculator: how many amps can the wire carry?

Pick the wire size and insulation rating, then add the ambient temperature and the number of conductors to get the adjusted ampacity and the share of it that your load uses.

Updated on
Your inputs
°F

Value out of range

A

Value out of range

Results

Adjusted ampacity

18.9 A

Load as a share of the adjusted ampacity

80%

Comfortable margin
Table ampacity
25 A
Ambient temperature factor
0.943
Conductor count factor
0.80
Protection limit for 14, 12 and 10 AWG
20 A

The size of a wire must match the current it carries, and heat is what limits that current. This wire ampacity calculator takes the wire size, the insulation temperature rating, the ambient temperature and the number of conductors in the conduit to give the adjusted ampacity in amps, the protection limit for small wires and the share of the ampacity that your load uses.

How the calculation works

  • Table ampacity is the current a copper conductor can carry in the U.S. National Electrical Code table 310.16, for the wire size and temperature rating you pick, at 86 °F (30 °C) ambient and with no more than 3 current-carrying conductors.
  • Ambient factor = √((rating − ambient) ÷ (rating − 30)), with temperatures in °C. It reproduces the code correction table: hotter surroundings leave less room for the heat of the current.
  • Conductor count factor = 1.0 for 1 to 3 conductors, 0.8 for 4 to 6, 0.7 for 7 to 9, 0.5 for 10 to 20, and so on.
  • Adjusted ampacity = table ampacity × ambient factor × conductor count factor. The share of the load = load current ÷ adjusted ampacity.

Example

A 12 AWG copper wire with 75 °C insulation has a table ampacity of 25 A. In an attic at 95 °F (35 °C) the factor is √(40 ÷ 45) = 0.943. With 6 conductors in the conduit the count factor is 0.8. The adjusted ampacity is 25 × 0.943 × 0.8 = 18.9 A. A 15 A load uses 80% of it.

Why it matters

Electricians and homeowners meet derating when they run several circuits in one conduit, pass a cable through a hot attic or use a wire close to its limit for a heater, a pump or an EV charger. A wire that is correct on the table can be overloaded once the conditions are added. The calculation shows the margin before the wire is pulled.

Good to know

This is a guide based on the U.S. National Electrical Code copper table and on the usual correction rules, and it is not a substitute for the code or for an electrician. It does not cover aluminum wire, wires in the earth or in the open air, motors with special rules, or voltage drop on long runs, which can call for a larger wire than the ampacity. Neutral conductors that carry only an imbalance do not always count as current-carrying. Terminals are usually limited to 60 or 75 °C, and local codes and inspectors may add rules, so check them before you build.

The wire size calculator picks a gauge for a load and a distance, the voltage drop version adds the losses on a long run and the conduit fill calculator checks that the wires fit in the pipe.

Frequently asked questions

What is ampacity?

Ampacity is the largest current a conductor can carry continuously without its insulation going over its temperature rating. It depends on the wire size, the insulation, the ambient temperature and the number of wires that share the heat.

Why does the ambient temperature matter?

A wire heats itself with the current and loses that heat to the air around it. In a hot attic there is less temperature difference to push heat away, so the wire has to carry less current. The code tables use 86 °F (30 °C) as the starting point.

Why does the number of conductors matter?

Wires bundled in one conduit or cable warm each other. With more than 3 current-carrying conductors, the code requires an adjustment that falls from 80% for 4 to 6 wires to 35% for 41 or more.

Can I use the 90 °C column for any wire?

Not always. The 90 °C column can be used as the starting point for derating, but the final value must not be higher than the rating of the terminals on the breaker and the devices, which is 60 or 75 °C in most equipment. Wires of 14, 12 and 10 AWG are also limited to 15, 20 and 30 A breakers.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.