Buried pipe earth load calculator: Marston load of the backfill on a pipe in a trench

Enter the trench width, the depth of fill, the soil weight and the soil type to get the Marston load coefficient, the earth load on the pipe, the weight of the soil prism and the average pressure at the top of a buried pipe.

Updated on
Your inputs
ft

Value out of range

ft

Value out of range

pcf

Value out of range

Results

Trench load on the pipe

1,915 lb/ft

Load coefficient Cd
1.773
Prism load (weight of the soil above the pipe)
2,880 lb/ft
Load as a share of the prism load
66.5 %
Average vertical pressure at the top of the pipe
638 psf

A pipe in a trench does not carry the whole weight of the soil above it: the friction on the trench walls helps. The buried pipe earth load calculator applies the Marston equation to give the load coefficient, the earth load on the pipe, the soil prism load for comparison and the average pressure at the top of the pipe.

How the calculation works

  • Enter the width of the trench at the top of the pipe, the depth of fill above the pipe and the unit weight of the backfill.
  • Select the soil type, which gives the product Kμ’ of the Rankine coefficient and the friction of the soil against the trench wall: 0.165 for granular soil, down to 0.110 for saturated clay.
  • The calculator applies the Marston equation for a trench: Wc = Cd γ Bd², with Cd = (1 − e^(−2 Kμ’ H / Bd)) / (2 Kμ’).
  • It gives the load coefficient, the load on the pipe, the weight of the soil prism above it and the average pressure at the top of the pipe.

Example

A trench of 3 ft of width is backfilled with 8 ft of a granular soil of 120 pcf (Kμ’ = 0.165). The load coefficient is Cd = (1 − e^(−2 × 0.165 × 8 / 3)) / (2 × 0.165) = 1.773. The trench load is Wc = 1.773 × 120 × 3² = 1,915 lb/ft. The prism of soil above the pipe weighs 120 × 8 × 3 = 2,880 lb/ft, so the pipe carries 66.5% of it. The average vertical pressure is 638 psf.

Why it matters

The calculator helps civil engineers, drainage contractors and students to estimate the dead load on a sewer, a culvert or a water main, and to see the effect of the trench width and the soil. It is the first step of the structural design of a buried pipe.

Good to know

Keep the trench narrow: a wider trench gives a higher load. Compact the backfill beside the pipe. Add the live load of traffic for shallow pipes. Check the strength of rigid pipes with the bedding factor, and the deflection of flexible pipes with the soil stiffness. Take the load that the pipe will see in its whole life.

The excavation calculator gives the volume of the trench, the soil compaction calculator covers the backfill, the culvert pipe size calculator sizes the pipe and the retaining wall calculator covers the lateral earth pressure.

Frequently asked questions

What is the Marston trench load?

The Marston theory gives the load of the backfill on a pipe in a narrow trench. The soil settles more than the pipe, and the friction between the backfill and the trench walls carries part of its weight, which is called the arching. So the load on the pipe is smaller than the weight of the soil prism above it. The load grows with the depth, but it approaches a limit for a very deep trench.

What does the coefficient Kμ' mean?

It is the product of the Rankine coefficient of the earth pressure K and the coefficient of friction μ' between the backfill and the sides of the trench. A larger value gives more friction, more arching and a smaller load. It is 0.165 for granular soils without cohesion, 0.150 for saturated top soil, 0.130 for ordinary clay and 0.110 for saturated clay. They are the standard values in the pipe design manuals.

Does it apply to wide trenches and embankments?

The equation is for a trench that is narrow, with a width less than the transition width. If the trench is wide, or if the pipe is under an embankment, the load is that of the embankment condition, with the settlement ratio and the projection of the pipe. The load is then often equal to or higher than the prism load. Use the narrow trench condition only when it applies.

What are the limits of this calculator?

It gives the dead load of the backfill only. It does not include the live loads of vehicles, the surcharge, the effect of the water table, the bedding, the stiffness of the pipe, the deflection or the buckling of a flexible pipe. For a real design, use the manual of the pipe type, such as the concrete, clay or plastic pipe design manuals, with the live load and the bedding factor.

Was this calculator helpful?