The buried pipe deflection calculator gives the soil prism pressure, the predicted vertical deflection and the ratio to the 5 % limit of a buried flexible pipe, with the modified Iowa formula, from the depth of cover, the weight of the soil, the stiffness of the pipe and the soil modulus.
How the calculation works
- Enter the depth of cover, the unit weight of the soil and the diameter of the buried flexible pipe.
- Enter the pipe stiffness, choose the soil modulus that fits the compaction of the bedding and choose the lag factor and the bedding constant.
- The calculator finds the soil prism pressure, the predicted deflection in percent and in inches, and the ratio to the 5 % limit.
Example
A PVC pipe of 12 in with a stiffness of 46 psi is buried under 8 ft of soil of 120 pcf, so the prism pressure is 120 × 8 / 144 = 6.67 psi. With a modulus E′ of 1,000 psi, a lag factor of 1.5 and K = 0.100, the deflection is 1.5 × 0.100 × 6.67 / (0.149 × 46 + 0.061 × 1,000) = 1.47 %, or 0.18 in for the 12 in pipe. This is 0.29 of the usual limit of 5 %.
Why it matters
The calculator helps pipeline and sewer designers, contractors, inspectors and students to check that a PVC, polyethylene or fiberglass pipe will keep its shape under the backfill, to choose the bedding and the compaction, and to compare the effect of the cover and of the stiffness of the pipe.
Good to know
Place the bedding and the backfill in thin layers, compact the haunches under the pipe by hand, and use a clean granular material in the pipe zone. Measure the deflection a few weeks after the backfilling, and with a mandrel for the final acceptance. Keep the trench wide enough for the compaction, and add the live load of the traffic when the pipe is under a road.
Related tools
The pipe wall thickness calculator checks the pipe for the internal pressure, the pipeline coverage calculator checks the minimum cover, the soil unit weight calculator converts the weights of the soil and the thrust block size calculator restrains the fittings.