The cable tray fill calculator checks that the cables fit in a cable tray according to NEC 392.22: the allowable fill area for the width of the tray, the cross-section of the cables, the fill percentage, the free area and the number of additional cables that can be added.
How the calculation works
- Choose the width of the ladder or ventilated trough cable tray.
- Enter the number and the outside diameter of the cables of two groups, for example power cables and control cables.
- The calculator finds the allowable fill area of NEC 392.22 for cables smaller than 4/0 AWG (7 in² per 6 in of width), the cross-section of all the cables, the fill percentage, the free area and the number of additional cables of group 2 that fit.
Example
A 12 in ladder tray allows 12 × 7 / 6 = 14.0 in². It holds 10 cables of 0.75 in (4.42 in²) and 6 cables of 1.10 in (5.70 in²), for a total of 10.1 in², or 72.3% of the allowed area. The free area is 3.9 in², which is enough for 4 more cables of 1.10 in.
Why it matters
The calculator helps electrical designers, contractors, estimators and facility managers to size a cable tray for a number of cables, to check an existing tray before adding a circuit and to compare widths. It avoids the overfilled trays that overheat and are hard to pull cables in.
Good to know
Use the real outside diameter of each cable from the datasheet, not the nominal size. Plan a spare capacity of 20 to 30% for future cables. Check the weight of the cables on the tray and its supports, and apply the derating of the ampacity for the cables in the tray. Follow the code of the country if it is not the NEC.
Related tools
The conduit fill calculator covers cables in a conduit, the wire ampacity calculator gives the current of a conductor, the wire size calculator sizes a conductor, and the wire size with voltage drop calculator checks the voltage drop.