Cable tray fill calculator: how many cables fit in a ladder or ventilated tray?

Choose the tray width and enter the number and diameter of two groups of cables to get the allowable fill area, the area of the cables, the fill percentage, the free area and the number of additional cables.

Updated on
Your inputs

Value out of range

in

Value out of range

Value out of range

in

Value out of range

Results

Fill of the allowable area

72.3 %

The tray fill is within the limit of NEC 392.22
Allowable fill area of the tray
14.0 in²
Cross-section of all the cables
10.1 in²
Free area remaining
3.9 in²
More cables of group 2 that fit
4

The cable tray fill calculator checks that the cables fit in a cable tray according to NEC 392.22: the allowable fill area for the width of the tray, the cross-section of the cables, the fill percentage, the free area and the number of additional cables that can be added.

How the calculation works

  • Choose the width of the ladder or ventilated trough cable tray.
  • Enter the number and the outside diameter of the cables of two groups, for example power cables and control cables.
  • The calculator finds the allowable fill area of NEC 392.22 for cables smaller than 4/0 AWG (7 in² per 6 in of width), the cross-section of all the cables, the fill percentage, the free area and the number of additional cables of group 2 that fit.

Example

A 12 in ladder tray allows 12 × 7 / 6 = 14.0 in². It holds 10 cables of 0.75 in (4.42 in²) and 6 cables of 1.10 in (5.70 in²), for a total of 10.1 in², or 72.3% of the allowed area. The free area is 3.9 in², which is enough for 4 more cables of 1.10 in.

Why it matters

The calculator helps electrical designers, contractors, estimators and facility managers to size a cable tray for a number of cables, to check an existing tray before adding a circuit and to compare widths. It avoids the overfilled trays that overheat and are hard to pull cables in.

Good to know

Use the real outside diameter of each cable from the datasheet, not the nominal size. Plan a spare capacity of 20 to 30% for future cables. Check the weight of the cables on the tray and its supports, and apply the derating of the ampacity for the cables in the tray. Follow the code of the country if it is not the NEC.

The conduit fill calculator covers cables in a conduit, the wire ampacity calculator gives the current of a conductor, the wire size calculator sizes a conductor, and the wire size with voltage drop calculator checks the voltage drop.

Frequently asked questions

What is the fill limit of a cable tray?

NEC 392.22 sets the maximum fill of a cable tray for multiconductor cables. For a ladder or ventilated trough tray with cables smaller than 4/0 AWG, the sum of the cross-sections must not exceed a value that is 7 in² for a 6 in tray and increases in proportion to the width, for example 14 in² for 12 in and 28 in² for 24 in. The limit leaves room for the heat to be dissipated and for the installation of the cables.

What about larger cables?

For cables of 4/0 AWG and larger, the NEC requires a single layer, and the sum of the diameters of the cables must not exceed the width of the tray. Other fill rules apply to a tray with a solid bottom, to single conductor cables, to a mix of small and large cables, and to a tray with a cover. The calculator applies only to the case of the small multiconductor cables in a ladder or ventilated tray.

Why does the fill matter for the ampacity?

The ampacity of cables in a tray depends on the spacing and on the number of cables. Cables that are bundled together heat each other, and the ampacity is reduced by derating factors, especially for more than three current-carrying conductors in a single tray. Keeping a fill well below the maximum, and separating the power cables from the control cables, improves the cooling and the ease of installation.

What are the limits of the calculator?

The calculator gives only the area check of the NEC for one common case. It does not compute the weight on the tray and its supports, the bending radius of the cables, the ampacity, the separation of the circuits of different voltages, or the fire stopping where the tray passes through a wall. The local code and the manufacturer’s data govern, and an electrical designer should approve the layout.