The conduit offset bend calculator gives the multiplier, the distance between the two marks, the shrink, the position of the second mark and the length of conduit to cut for an offset bend of an EMT or a rigid conduit, from the height of the offset and the angle of the bends.
How the calculation works
- Enter the height of the offset, that is the distance to move the conduit, and choose the angle of the bends.
- Enter the distance from the end of the conduit to the first mark and the length of the straight run you need.
- The calculator finds the multiplier, the distance between the marks, the shrink, the second mark and the length to cut.
Example
To move a conduit by 6 in with 30 degree bends, the multiplier is 1 / sin 30° = 2.00, so the marks are 12.0 in apart. The first mark is at 30 in from the end, so the second one is at 42.0 in. The offset shortens the conduit by 6 × (1 − cos 30°) / sin 30° = 1.61 in, so a straight run of 120 in needs a conduit of 121.61 in.
Why it matters
The calculator helps electricians, apprentices, instructors and students to mark an offset quickly, to check the multiplier and the shrink of the usual angles, and to cut the conduit to the right length before the bending on the site.
Good to know
Mark the conduit on the flat side and use the same direction of the bender for both bends. Keep the conduit in the same plane while you bend it, and rotate it by exactly half a turn for the second bend. Make a test offset on a scrap of conduit, and check the height with a tape before you fix the conduit.
Related tools
The conduit fill calculator checks the number of conductors in a conduit, the cable tray fill calculator checks a cable tray, the wire size calculator gives the size of a conductor and the rolling offset calculator gives the length of a pipe offset in two planes.