The time that water stays in a tank sets how well it settles, mixes or disinfects. The detention time calculator takes the tank volume, the flow rate, the surface area and the weir length and gives the detention time, the surface overflow rate and the weir loading, with a note on the overflow rate.
How the calculation works
- Detention time (hydraulic retention time) = tank volume ÷ flow rate. It is the average time that water spends in the tank.
- Surface overflow rate = flow rate ÷ surface area of the tank. It is the speed at which water rises, and a particle settles out if it sinks faster than this. Here it is in gallons per day per square foot.
- Weir loading = flow rate ÷ weir length, in gallons per day per foot. A high loading pulls solids over the weir.
- The calculation converts every input to cubic metres and hours, then gives the result in US units.
Example
A clarifier holds 300 000 gal and receives 500 gpm, with a surface area of 1 800 ft² and a weir length of 120 ft. The detention time is 300 000 ÷ (500 × 60) = 10 hours. The surface overflow rate is 500 × 1 440 ÷ 1 800 = 400 gpd/ft², comfortable for most clarifiers, and the weir loading is 500 × 1 440 ÷ 120 = 6 000 gpd/ft.
Why it matters
Operators and designers use these three numbers to check that a clarifier or basin is not overloaded when the flow increases, to compare a plant with its design, and to decide whether to put a tank in service or take one out. The same maths applies to a settling pond or a storage tank.
Good to know
The figures are averages that assume even flow through the whole tank, without short-circuiting or dead zones. The rules on the overflow rate are rough guides, since the design depends on the type of solids, the temperature and the local standards. Use the peak flow as well as the average, because that is what usually causes a failure.
Related tools
The activated sludge calculator sizes the biological treatment ahead of a clarifier and the septic tank calculator sizes a small tank for a house.