The duct leakage calculator gives the allowable leakage of a duct system from the SMACNA leakage class, the duct surface and the static pressure, in cfm per 100 ft² and for the whole duct, with its percentage of the system airflow.
How the calculation works
- Choose the leakage class CL of the duct, from the sealing specified in SMACNA: a lower class means a tighter duct.
- Enter the surface area of the duct, the static pressure at which it operates and the airflow of the system.
- The calculator finds the leakage per 100 ft² with the SMACNA equation Q = CL × P^0.65, the allowable leakage of the whole duct and its share of the system airflow.
Example
A duct system of 5,000 ft² of surface is built to CL 6 and operates at 2.0 in. w.c. The leakage per 100 ft² is 6 × 2^0.65 = 9.4 cfm. For the whole duct, the allowable leakage is 9.4 × 50 = 471 cfm. With a system airflow of 10,000 cfm, this is 4.7%, which is below the 5% that is often the target.
Why it matters
The calculator helps HVAC designers, contractors, energy auditors and commissioning agents to choose the leakage class of a duct system, to see how much air a specification allows to leak and to compare the cost of sealing with the loss of energy. It also helps to prepare the leakage test of the ducts.
Good to know
Seal all the seams and joints, the longitudinal ones included, with a mastic or a tape listed for the duct, and keep the ducts away from unconditioned spaces. Test the leakage of a representative part of the system before the insulation and the finishes are installed. Choose a class that matches the pressure of the duct and the energy code in force.
Related tools
The duct size calculator sizes the duct for the airflow, the air changes calculator gives ventilation rates, the HRV installation cost calculator covers heat recovery ventilation and the kitchen hood exhaust airflow calculator covers a commercial hood.