Duct leakage calculator: how much air may a duct system leak?

Choose the leakage class and enter the duct surface, the static pressure and the system airflow to get the leakage per 100 ft², the allowable leakage of the duct and its percentage of the airflow.

Updated on
Your inputs
ft²

Value out of range

in. w.c.

Value out of range

cfm

Value out of range

Results

Leakage over the system airflow

4.7 %

The leakage is low: below 5% of the airflow
Leakage per 100 ft² of duct
9.4 cfm
Allowable leakage of the duct
471 cfm

The duct leakage calculator gives the allowable leakage of a duct system from the SMACNA leakage class, the duct surface and the static pressure, in cfm per 100 ft² and for the whole duct, with its percentage of the system airflow.

How the calculation works

  • Choose the leakage class CL of the duct, from the sealing specified in SMACNA: a lower class means a tighter duct.
  • Enter the surface area of the duct, the static pressure at which it operates and the airflow of the system.
  • The calculator finds the leakage per 100 ft² with the SMACNA equation Q = CL × P^0.65, the allowable leakage of the whole duct and its share of the system airflow.

Example

A duct system of 5,000 ft² of surface is built to CL 6 and operates at 2.0 in. w.c. The leakage per 100 ft² is 6 × 2^0.65 = 9.4 cfm. For the whole duct, the allowable leakage is 9.4 × 50 = 471 cfm. With a system airflow of 10,000 cfm, this is 4.7%, which is below the 5% that is often the target.

Why it matters

The calculator helps HVAC designers, contractors, energy auditors and commissioning agents to choose the leakage class of a duct system, to see how much air a specification allows to leak and to compare the cost of sealing with the loss of energy. It also helps to prepare the leakage test of the ducts.

Good to know

Seal all the seams and joints, the longitudinal ones included, with a mastic or a tape listed for the duct, and keep the ducts away from unconditioned spaces. Test the leakage of a representative part of the system before the insulation and the finishes are installed. Choose a class that matches the pressure of the duct and the energy code in force.

The duct size calculator sizes the duct for the airflow, the air changes calculator gives ventilation rates, the HRV installation cost calculator covers heat recovery ventilation and the kitchen hood exhaust airflow calculator covers a commercial hood.

Frequently asked questions

What is the leakage class?

The leakage class CL of SMACNA is the leakage in cfm per 100 ft² of duct surface at a static pressure of 1 in. w.c. For example a duct of CL 6 leaks 6 cfm per 100 ft² at 1 in. The class depends on the type of the duct and on the sealing of the seams and the joints: round ducts are the tightest, and rectangular ducts without sealant are the leakiest. The specification of the project states the class to be reached and tested.

How does the leakage change with the pressure?

The leakage increases with the pressure but less than proportionally, following the equation Q = CL × P^0.65. If the pressure is doubled, the leakage is multiplied by 1.57. This is why the high-pressure ducts need a tighter class than the low-pressure ducts, and why the leakage test is made at the working pressure of the duct, or at the test pressure of the specification.

Why does the leakage matter?

Air that leaks from a supply duct is conditioned air that does not reach the rooms. A leakage of 10 to 20%, common in old systems, means that the fan and the cooling equipment must be larger and use more energy, and the rooms can be unbalanced. Energy codes ask for ducts sealed to a given class, or for a total leakage that is a small share, such as 4 cfm per 100 ft² of conditioned floor area.

What are the limits of the calculator?

The calculator gives the allowable leakage from the class, not the measured leakage of an installed duct, which must be tested with a calibrated fan according to the SMACNA or the local procedure. The real leakage depends on the quality of the work and on the fittings and the access doors. Leakage to an unconditioned space is a loss, and leakage to the conditioned space is not, so the test also depends on the code used.