Pump operating point calculator: the flow and head a pump will really give

Enter the shutoff head, the rated point of a pump, and the static and friction head of the piping system to get the operating flow and head, the position on the curve, the friction head and the power absorbed.

Updated on
Your inputs
ft

Value out of range

gpm

Value out of range

ft

Value out of range

ft

Value out of range

ft

Value out of range

%

Value out of range

Results

Operating flow

443.8 gpm

Operating head
83.08 ft
Operating flow as a share of the rated flow
110.9 %
Within the usual operating range of the pump
Friction head of the system at that flow
43.08 ft
Power absorbed by the pump (water)
13.30 hp

A pump works at the intersection of its curve and the system curve of the piping. The pump operating point calculator models both curves from a few known points to find the operating flow and head, the position relative to the rated flow, the friction head and the power absorbed.

How the calculation works

  • Enter the shutoff head of the pump (the head at zero flow), its rated flow and the head at the rated flow, from the manufacturer’s curve.
  • Enter the static head of the system (the elevation difference plus the pressure to be delivered) and its friction head at the rated flow.
  • The calculator models the pump curve as H = H0 − a Q² and the system curve as H = Hs + K Q², and finds their intersection, the operating point: Q = √[(H0 − Hs) / (a + K)].
  • It gives the flow, the head, the position relative to the rated flow, the friction head at that flow and the power absorbed by the pump for a given efficiency.

Example

A pump has a shutoff head of 120 ft and gives 90 ft at 400 gpm. The system has a static head of 40 ft and a friction head of 35 ft at 400 gpm. The pump curve coefficient is a = 30 / 400² = 0.0001875 and the system coefficient is K = 35 / 400² = 0.00021875. The operating flow is √[(120 − 40) / (0.0001875 + 0.00021875)] = 443.8 gpm, at a head of 83.08 ft. That is 110.9% of the rated flow. The friction head is 43.08 ft and, at 70% efficiency, the pump absorbs 13.30 hp.

Why it matters

The calculator helps plumbers, mechanical and process engineers, facility managers and students to predict the flow that a pump will give in a piping system, to see the effect of a change in the static head or the friction, and to check if the pump works in a healthy range. It avoids the error of reading the rated flow as the actual flow.

Good to know

Take the points of the pump curve from the manufacturer’s data for the impeller installed. Compute the friction head with the real piping, fittings and valves at the design flow. Check the net positive suction head at the flow found. Leave a margin of 5% to 10% on the head, but do not oversize the pump much, since it then works far to the right of its curve.

The pump power calculator gives the shaft power and cost, the NPSH calculator checks the suction, the fan affinity laws calculator shows how speed changes the curve and the valve Cv calculator sizes the control valve that moves the system curve.

Frequently asked questions

What is the operating point of a pump?

A pump and the piping it serves always settle at the flow where the head that the pump provides is equal to the head that the system needs. Graphically, it is the intersection of the pump curve, which falls with the flow, and the system curve, which rises with the flow. If the system changes, for example when a valve closes or a filter clogs, the system curve moves and the operating point moves along the pump curve.

What is the system curve?

The system curve is the head needed to move a given flow through the piping: the static head, which does not depend on the flow, plus the friction head, which grows with the square of the flow. In this calculator the friction is scaled from one known point, at the rated flow, assuming a square law. It is accurate for turbulent flow in a fixed piping, and less when the flow is low or the control valves change position.

Why check the position on the pump curve?

A pump works best near its best efficiency point, usually close to the rated flow. Far to the left of it, at a low flow, the pump heats the fluid, recirculates internally and vibrates, and the bearings and seals wear. Far to the right, at a high flow, the net positive suction head required rises, the pump can cavitate and the motor can overload. The usual advice is to stay between 70% and 120% of the rated flow.

What are the limits of this calculator?

The pump curve is approximated by a parabola through the shutoff point and the rated point, which is good near the rated point but not exact at the extremes. The model ignores the change of efficiency along the curve, which is why the power uses one efficiency. For parallel or series pumps, a variable speed or a viscous fluid, build the curves point by point from the manufacturer’s data.