Hydronic expansion tank calculator: size the expansion tank of a heating system

Enter the water volume, the cold and hot temperatures and the fill and maximum pressures of a closed heating loop to get the water expansion and the minimum volume of the diaphragm expansion tank.

Updated on
Your inputs
gal

Value out of range

°F

Value out of range

°F

Value out of range

psig

Value out of range

psig

Value out of range

Results

Minimum expansion tank volume

3.76 gal

Water expansion
3.03 %
Volume of expanded water
1.52 gal
Acceptance factor 1 − Pfill / Pmax (absolute)
0.403

Water expands when it is heated, and a closed heating loop needs a tank to take that extra volume. The hydronic expansion tank calculator computes the water expansion from the density at the cold and hot temperatures, and the minimum volume of the diaphragm expansion tank from the fill and maximum pressures.

How the calculation works

  • Enter the water volume of the heating system, from the boiler, the pipes and the radiators. A rough value is 1 to 2 gallons per 10,000 Btu/h in a residential system.
  • Enter the cold temperature at fill and the maximum temperature of the water in operation.
  • Enter the fill pressure (the pressure of the cold system at the tank, which is also the precharge of the diaphragm) and the maximum pressure, which is usually slightly below the setting of the relief valve.
  • The calculator computes the water expansion from the density at both temperatures, then the tank volume Vt = V × expansion / (1 − Pfill / Pmax) with absolute pressures.

Example

A closed hydronic system of 50 gal is filled at 50 °F and heated to 180 °F. The density of water falls from 999.7 to 970.3 kg/m³, so the expansion is 3.03%, or 1.52 gal. The fill pressure is 12 psig (26.7 psia) and the maximum pressure is 30 psig (44.7 psia). The acceptance factor is 1 − 26.7 / 44.7 = 0.403. The minimum tank volume is 1.52 / 0.403 = 3.76 gal. A standard tank of 4.4 gal or more would be chosen.

Why it matters

The calculator helps plumbers, heating technicians, homeowners and engineering students to size or to check the expansion tank of a boiler loop, a radiant floor or a chilled water circuit. It shows how the pressures and the temperatures change the tank size, with the physical property of water and not a rule of thumb.

Good to know

Use a fill pressure that is high enough to keep the highest point of the loop above atmospheric pressure, about 12 psig for a two-floor house. Keep the maximum pressure at least 5 psi below the relief valve setting. Round the result up to the next standard tank, and use glycol data if the loop has antifreeze.

The pressure tank calculator covers well pumps, the boiler size calculator sizes the heat source, the water heater size calculator covers domestic hot water and the hydrostatic pressure calculator gives the pressure at the highest point.

Frequently asked questions

Why does a heating system need an expansion tank?

Water expands when heated, and the system is closed. Without a tank, the extra volume of water raises the pressure until the relief valve opens, which wastes water and can let air into the loop. A diaphragm expansion tank has a cushion of air or nitrogen behind a rubber membrane. It takes the extra water by compressing the gas, which keeps the pressure within the allowed range.

How is the expansion tank volume found?

The volume is Vt = V × ε / (1 − Pi / Pf), where V is the water volume of the system, ε is the relative expansion of the water between the cold and the hot temperature, Pi is the fill pressure (the precharge) and Pf is the maximum pressure, both absolute. The factor 1 − Pi / Pf is the part of the tank that can take water between those two pressures. A lower fill pressure or a higher maximum pressure gives a smaller tank.

What precharge should the tank have?

The precharge of the air side must be equal to the fill pressure of the system at the tank, with the system not filled, so that the diaphragm starts to move as the water heats. Check the precharge with the system isolated and the water side empty, since a tank can lose its air with time. A tank with a low precharge will fill with water too soon, and a tank with a high one will not take the full expansion.

What are the limits of this calculator?

It uses the density of pure water. A glycol mixture expands more, up to two or three times the value for water, so use the data of the mixture. The calculator also does not include the margin for the loss of gas with time, the expansion of the pipes, the vertical position of the tank, or the tank sizing rules of a specific code. Check the manufacturer’s tables and add a margin for safety.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.