Mixed air temperature calculator: what temperature enters the coil?

Enter the return and outdoor air temperatures and flows to get the mixed air temperature, the outdoor air share and the sensible load to reach the supply temperature.

Updated on
Your inputs
°F

Value out of range

CFM

Value out of range

°F

Value out of range

CFM

Value out of range

°F

Value out of range

Results

Mixed air temperature

79.00 °F

Outdoor air share of the total flow
20.0 %
Total air flow
5,000 CFM
Sensible load to reach the supply temperature (negative = cooling)
-129,600 BTU/h
Sensible load added by the outdoor air alone
21,600 BTU/h

Before air reaches the coil, the fresh air and the return air have mixed. The mixed air temperature calculator takes the return air and outdoor air temperatures and flows plus a supply air temperature, and gives the mixed air temperature, the outdoor air share, the total flow, the sensible load to reach the supply temperature and the load added by the outdoor air.

How the calculation works

  • Enter the return air temperature and flow, which is the air coming back from the building, and the outdoor air temperature and flow, which is the fresh air brought in for ventilation.
  • The mixed air temperature is the flow-weighted average: T mix = (Q return × T return + Q outdoor × T outdoor) ÷ (Q return + Q outdoor).
  • The outdoor air share is the outdoor flow divided by the total flow. It is often 10 to 30 % in an office.
  • Enter the supply air temperature you want to see the sensible load on the coil, using Q = 1.08 × CFM × ΔT in BTU/h, and the part of the load that comes from the outdoor air.

Example

An air handler receives 4,000 CFM of return air at 75 °F and 1,000 CFM of outdoor air at 95 °F. The mixed air is (4,000 × 75 + 1,000 × 95) ÷ 5,000 = 79 °F, and the outdoor air is 20 % of the 5,000 CFM total. To reach a supply temperature of 55 °F, the coil removes 1.08 × 5,000 × (55 − 79) = 129,600 BTU/h. The outdoor air alone adds 1.08 × 1,000 × 20 = 21,600 BTU/h.

Why it matters

HVAC designers and technicians use the mixed air temperature to size coils, check economizer operation and troubleshoot air handlers. A mixed air reading that does not match the calculation can point to a leaking damper or a poor sensor position.

Good to know

The result is for sensible heat and dry-bulb temperatures at roughly standard air density. Humidity, altitude, stratification of the mixed stream and leaks all change the real value. Measure the temperature at several points of the duct for a reliable reading.

The air changes calculator relates airflow to room volume, and the duct size calculator sizes the ducts that carry it.

Frequently asked questions

How is the mixed air temperature calculated?

It is the average of the two air temperatures weighted by their flows: (Q return × T return + Q outdoor × T outdoor) ÷ (Q return + Q outdoor). The formula is exact for dry-bulb temperature when the air density is roughly the same in both streams.

What is the sensible heat formula 1.08 × CFM × ΔT?

It gives the heat in BTU per hour needed to change the temperature of air flowing at a given CFM by ΔT degrees Fahrenheit. The 1.08 factor combines the density and the specific heat of standard air. In SI units, the factor is about 0.34 W per cubic meter per hour and per kelvin.

Why is the outdoor air fraction important?

Ventilation codes require a minimum of outdoor air to dilute pollutants and carbon dioxide. This air has to be heated or cooled, so a higher share raises the load on the coil. An economizer increases the share when the outdoor air is cool enough to help.

Does this include humidity?

No. The calculator treats sensible heat only, with dry-bulb temperatures. Cooling humid outdoor air also takes out moisture, which adds a latent load that can be large in humid climates. A psychrometric calculation is needed for the full load.

Was this calculator helpful?

Thanks for your feedback!

Results are estimates provided for information purposes. They do not replace professional advice.