Before air reaches the coil, the fresh air and the return air have mixed. The mixed air temperature calculator takes the return air and outdoor air temperatures and flows plus a supply air temperature, and gives the mixed air temperature, the outdoor air share, the total flow, the sensible load to reach the supply temperature and the load added by the outdoor air.
How the calculation works
- Enter the return air temperature and flow, which is the air coming back from the building, and the outdoor air temperature and flow, which is the fresh air brought in for ventilation.
- The mixed air temperature is the flow-weighted average: T mix = (Q return × T return + Q outdoor × T outdoor) ÷ (Q return + Q outdoor).
- The outdoor air share is the outdoor flow divided by the total flow. It is often 10 to 30 % in an office.
- Enter the supply air temperature you want to see the sensible load on the coil, using Q = 1.08 × CFM × ΔT in BTU/h, and the part of the load that comes from the outdoor air.
Example
An air handler receives 4,000 CFM of return air at 75 °F and 1,000 CFM of outdoor air at 95 °F. The mixed air is (4,000 × 75 + 1,000 × 95) ÷ 5,000 = 79 °F, and the outdoor air is 20 % of the 5,000 CFM total. To reach a supply temperature of 55 °F, the coil removes 1.08 × 5,000 × (55 − 79) = 129,600 BTU/h. The outdoor air alone adds 1.08 × 1,000 × 20 = 21,600 BTU/h.
Why it matters
HVAC designers and technicians use the mixed air temperature to size coils, check economizer operation and troubleshoot air handlers. A mixed air reading that does not match the calculation can point to a leaking damper or a poor sensor position.
Good to know
The result is for sensible heat and dry-bulb temperatures at roughly standard air density. Humidity, altitude, stratification of the mixed stream and leaks all change the real value. Measure the temperature at several points of the duct for a reliable reading.
Related tools
The air changes calculator relates airflow to room volume, and the duct size calculator sizes the ducts that carry it.