Negative air machine count calculator for a containment

Enter the size of the containment, the air changes per hour and the rated airflow of the machine to get the airflow required, the number of negative air machines and the clearance time.

Updated on
Your inputs
ft

Value out of range

ft

Value out of range

ft

Value out of range

ACH

Value out of range

cfm

Value out of range

Value out of range

Results

Machines needed

2

Volume of the containment
24,000 ft³
Airflow required
2,400 cfm
Machines to bring (with the spare)
3
Air changes per hour of the machines brought
10.5 ACH
Time to clear 99 % of the dust (ideal mixing)
46.1 min

The negative air machine calculator gives the airflow required for the air changes per hour of a containment, the number of HEPA negative air machines with a derating for loaded filters and a spare, and the time to clear the air.

How the calculation works

  • Enter the length, width and height of the containment, the air changes per hour required and the airflow rated for one machine.
  • Enter the derating for loaded filters and choose whether to bring a spare machine.
  • The calculator gives the airflow required, the number of negative air machines, the number with the spare and the time to clear the air.

Example

A containment of 60 ft × 40 ft × 10 ft has a volume of 24,000 ft³. At 6 air changes per hour it needs 24,000 × 6 / 60 = 2,400 cfm. A machine rated at 2,000 cfm with a derating of 0.7 moves 1,400 cfm, so the job needs 2 machines and 3 with the spare. The machines brought give 10.5 air changes per hour, and with ideal mixing the air clears 99 % of the dust in about 46 minutes.

Why it matters

The calculator helps abatement contractors, restoration firms, industrial hygienists and project managers to size the equipment of a dust or hazard containment, to price the rental and to check the plan against the specification.

Good to know

Use the volume of the containment, not of the whole building, and subtract large objects that take up space only if they are a big share of it. Take the rated airflow from the data sheet of the machine at the working static pressure, not the free air value. Place the machines so that air sweeps through the whole area, with the makeup air entering far from the exhaust, and verify the negative pressure with a manometer at the entry. A spare machine is cheap compared with the cost of a shutdown if one fails during the work. The pressure difference, not the count, is the proof that the containment works.

The confined space purge calculator gives the time to ventilate a space, the air changes calculator gives the ventilation of a room, the asbestos removal cost calculator prices an abatement and the lead paint removal cost calculator prices a lead job.

Frequently asked questions

What is a negative air machine?

A negative air machine is a fan with a HEPA filter that draws the air out of a work area and exhausts it outside or filters it before it goes back. It lowers the pressure inside the containment so that air flows in through the gaps and the dust does not leak out. It is used for asbestos, lead, mold, silica and demolition dust.

How many air changes do I need?

The usual design value for abatement is at least 4 air changes per hour, and many specifications ask for 6 or more, with a pressure difference of at least 0.02 inch of water column between the inside and the outside. The specification of the project or the rule of the authority decides. Large or dusty work needs more.

Why derate the machine?

The rated airflow is measured with clean filters and no resistance. As the pre-filters and the HEPA filter load with dust, the flow falls, and long ducts and bends add resistance. A derating of 0.7 means that the machine gives 70 % of its rating, so the count is based on the flow you can rely on and not on the label.

What does the calculator leave out?

The calculator leaves out the makeup air openings, the pressure difference that you must verify with a manometer, the leakage of the containment, the ducting losses and the exhaust path. The clearance time assumes ideal mixing, which a real room does not have, so use it as a guide only.